The Schneider Electric A9Z14480 is an Acti9 iID residual current circuit breaker (RCCB) — a 4-pole, 80 A unit with 300 mA sensitivity, Type AC earth-leakage protection. The 1500 A making/breaking capacity (Idm/Im) is enough for most sub-distribution boards — no need to oversize the upstream breaker unless the fault current exceeds that level. The 300 mA sensitivity is a common choice for general-purpose protection where equipment leakage (motors, heaters, VFDs) would nuisance-trip a 30 mA device. It's instantaneous, so it clears fast on a direct fault to earth.
Neutral is on the left — standard for Acti9 4P RCCBs. IP20 on the front, IP40 inside a modular enclosure — fine for dry indoor panels.