Skip to main content
Schneider Electric A9Z15491 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z15491 Acti9 iID RCCB, 4P, 100 A, 300 m

MPNA9Z15491
Obsolete

Schneider Electric Acti9 iID, Residual current circuit breaker (RCCB), 4P, 100 A, 300 mA, Type AC, selective, 380...415 V AC, IP20, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z15491 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
A9Z15491 — Electrical Ratings
ParameterValue
Rated current (In)100 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z15491 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z15491 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height91 mm
Depth73 mm
A9Z15491 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z15491 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9Z15491 is a 4-pole (4P) Acti9 iID residual current circuit breaker (RCCB) rated for 100 A continuous current at 380–415 V AC, 50/60 Hz. The selective (time-delay) characteristic provides coordination with downstream 30 mA RCCBs, preventing nuisance tripping on transient leakage while still clearing a sustained fault within the standard disconnection time. Rated breaking and making capacity is 1500 A (Idm/Im), and the conditional short-circuit current withstand is 10 kA — adequate for most commercial and industrial sub-distribution boards where the upstream protective device limits prospective fault current. The voltage-independent tripping technology means the RCCB detects leakage even if the phase voltage collapses, a critical safety feature for earth faults that pull down the supply.

The white housing carries a toggle control and a contact-position indicator. Terminals accept double conductors up to 35 mm² rigid (front) or 25 mm² flexible, with a stripping length of 14 mm and tightening torque of 3.5 N·m. IP20 finger-safe terminals; IP40 within a modular enclosure — standard for panel mounting in dry indoor switchboards.

Electrical durability is 10,000 cycles under AC-1 (resistive load); mechanical durability is 20,000 cycles. The padlocking device provision allows lockout/tagout for maintenance isolation.

Frequently asked questions

Where can I buy A9Z15491 and how do I get a price?

The A9Z15491 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is A9Z15491's listed depth (73 mm) on this component line?

The A9Z15491 has a depth of 73 mm, a width of 72 mm (8 x 9 mm pitches), and a height of 91 mm.

What is A9Z15491's listed range (Acti9) on this component line?

The A9Z15491 belongs to the Acti9 range from Schneider Electric, specifically the iID series of residual current circuit breakers (RCCBs).

What compliance documentation does this brand provide for A9Z15491 (RoHS, REACH, UL, IEC)?

The A9Z15491 is designed and certified to EN/IEC 61008-1 and EN/IEC 61008-2-1. The evidence does not list RoHS, REACH, or UL marks specifically, but the IEC standards are the primary compliance framework for this part in European and many international markets.

MPN
A9Z15491