Skip to main content
Schneider Electric A9Z24240 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z24240 Acti9 iID RCCB, 40A 300mA Type A

MPNA9Z24240
Active

Schneider Electric Acti9 iID, A9Z24240, 2P RCCB, 40 A, 300 mA Type A, 10 kA conditional short-circuit current, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z24240 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z24240 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z24240 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z24240 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73 mm
A9Z24240 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z24240 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9Z24240 is an Acti9 iID 2-pole residual current circuit breaker (RCCB) rated at 40 A with a 300 mA Type A earth-leakage sensitivity. Rated operational voltage is 220...240 V AC at 50/60 Hz, with a rated insulation voltage of 500 V AC and an impulse withstand voltage of 6 kV. The conditional short-circuit current is 10 kA, and the rated breaking and making capacity is 1500 A (Idm/Im). This is a voltage-independent, instantaneous-trip RCCB, meaning it detects earth leakage without needing an external power supply and trips without intentional delay. The Type A classification covers sinusoidal AC residual currents and pulsating DC residual currents up to 6 mA.

IP20 protection conforming to IEC 60529 on the device body; IP40 when installed in a modular enclosure. The 8/20 µs impulse withstand rating of 250 A per EN/IEC 61008-1 confirms immunity to common surge waveforms.

Installation and wiring

Clip-on mounting to DIN rail. Neutral is on the left side. Strip length is 14 mm for both top and bottom connections. The toggle control provides a contact position indicator. A padlocking device can be fitted for lockout/tagout procedures.

Frequently asked questions

What is A9Z24240's rated current and earth-leakage sensitivity?

The A9Z24240 is rated at 40 A with a 300 mA Type A earth-leakage sensitivity.

What standards does the A9Z24240 comply with?

The A9Z24240 complies with EN/IEC 61008-1 and EN/IEC 61008-2-1 for residual current operated circuit-breakers.

MPN
A9Z24240