Specifications

A9Z24263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z24263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z24263 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z24263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73 mm
A9Z24263 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z24263 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9Z24263 is a 2-pole residual current circuit breaker (RCCB) from the Acti9 iID family, rated 63 A with 300 mA earth-leakage sensitivity. The 300 mA threshold is the standard choice for whole-circuit protection in commercial and industrial sub-distribution boards — it tolerates normal leakage from power supplies and motor drives without nuisance tripping, unlike a 30 mA unit which is sized for personal shock protection on socket-outlet circuits. Type A detection means it catches sinusoidal AC faults plus pulsating DC faults up to 6 mA smooth DC superimposed, covering the rectified waveforms from single-phase electronics and variable-speed drives. Voltage-independent tripping means the device disconnects on earth leakage even if the line voltage collapses, a reliability advantage over electronically-triggered units.

Clip-on mounting to DIN rail, 36 mm width (4 x 9 mm pitches), 91 mm height, 73 mm depth. Occupies two modular spaces in a standard enclosure. Neutral on the left. Tightening torque 3.5 N.m. IP20 finger-safe on the front; IP40 within a modular enclosure. Padlocking device provision for lockout/tagout during maintenance.

Frequently asked questions

What is the A9Z24263 used for?

It is a 2-pole residual current circuit breaker (RCCB) for AC networks at 220-240 V, 50/60 Hz. The 300 mA sensitivity and Type A detection make it suited for whole-circuit earth-leakage protection in commercial and industrial sub-distribution boards where normal leakage from electronics and drives is present.

What is the closest alternative to the A9Z24263 in the Acti9 family?

Within the Acti9 iID range, the closest sibling is a 2P RCCB with the same 300 mA sensitivity but a lower current rating (e.g., 40 A or 25 A) for smaller sub-circuits, or a 30 mA version for personal shock protection on socket circuits. The A9Z24263 at 63 A is the high-current variant for main incomer or heavy-load sub-feed protection.

Where can I buy the A9Z24263?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time.