Rated 40 A continuous with a 300 mA earth-leakage sensitivity, Type A protection means it catches sinusoidal AC faults plus pulsating DC faults, which covers most modern electronics and variable-speed drives. The selective time delay is the key fit detail: it holds through short-duration earth faults so the downstream RCCB trips first, keeping the upstream supply live for the rest of the board. That coordination matters when you're feeding multiple sub-distribution boards off one main RCCB.
Neutral on the left. IP20 body, IP40 inside a modular enclosure — fine for dry indoor panels, not for washdown. Tightening torque 3.5 N.m top or bottom.
Rated impulse withstand voltage 6 kV, conditional short-circuit current 10 kA.