Skip to main content
Schneider Electric A9Z25263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z25263 Acti9 iID RCCB, 63 A, 300 mA, Ty

MPNA9Z25263
Obsolete

Schneider Electric Acti9 iID, A9Z25263, 2P RCCB, 63 A rated current, 300 mA Type A earth-leakage sensitivity, selective time delay, DIN-rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z25263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
A9Z25263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z25263 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z25263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73 mm
A9Z25263 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z25263 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The A9Z25263 is a 2-pole residual current circuit breaker (RCCB) from the Acti9 iID series, rated 63 A continuous current with a 300 mA Type A earth-leakage sensitivity and selective time delay. The 63 A frame covers the main incoming feeder or sub-feed for a distribution board on a 220–240 V AC 50/60 Hz network. The selective (S-type) delay coordinates with downstream RCCBs: it holds off tripping for a short interval so the downstream device clears first, keeping the upstream supply alive for the rest of the panel. Rated conditional short-circuit current is 10 kA (Idm 1500 A, Im 1500 A), and the insulation voltage is 500 V AC with impulse withstand at 6 kV. The enclosure itself carries IP40 when fitted in a modular enclosure, so it suits clean, dry cabinet installations.

Neutral is on the left. Terminals accept double conductor entry: front terminals 1–35 mm² rigid, 1–25 mm² flexible; back terminals 1–25 mm² rigid. The toggle control, contact position indicator, and padlocking provision are standard for lockout/tagout.

Frequently asked questions

Where can I buy A9Z25263?

The A9Z25263 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the difference between Type A and Type AC RCCBs for this part?

Type A detects both sinusoidal AC and pulsed DC residual currents, while Type AC detects only sinusoidal AC. The A9Z25263 is Type A, so it covers loads with rectified waveforms (e.g., switching power supplies, LED drivers).

What does the selective time delay mean on the A9Z25263?

Selective (S-type) delay means the RCCB holds off tripping for a short interval to allow downstream RCCBs to clear first, providing coordination and preventing an upstream trip that would take out the whole panel.

MPN
A9Z25263