Skip to main content
Schneider Electric A9Z25480 — Residual Current Breakers (RCCB/RCBO)

A9Z25480 Acti9 iID 4P 80A 300mA Type A RCCB, Selective

MPNA9Z25480
Active

Schneider Electric Acti9 iID A9Z25480, 4P RCCB, 80 A, 300 mA Type A, selective time delay, 380-415 V AC, 10 kA SCCR, DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z25480 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
A9Z25480 — Electrical Ratings
ParameterValue
Rated current (In)80 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z25480 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z25480 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height91 mm
Depth73 mm
A9Z25480 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z25480 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9Z25480 is a 4-pole residual current circuit breaker (RCCB) from the Acti9 iID series, rated at 80 A with 300 mA earth-leakage sensitivity and Type A protection — meaning it trips on sinusoidal AC and pulsating DC residual currents, which covers most modern electronic loads like VFDs, switched-mode supplies, and LED drivers. The selective (S-type) time delay prevents nuisance tripping on short-duration leakage pulses, so this unit coordinates downstream with faster RCCBs or RCBOs in a distribution board. Rated operational voltage is 380...415 V AC at 50/60 Hz, with a conditional short-circuit current (Icc) of 10 kA — enough for typical commercial and light industrial panels where the upstream breaker provides the fault clearance. The voltage-independent tripping mechanism means it operates without an external power supply, so a loss of neutral or line voltage won't disable the earth-leakage protection. The IP20 finger-safe terminals (IP40 in modular enclosure) suit indoor panel use.

The A9Z25480 is current-production in the Schneider Electric Acti9 range. No end-of-life notification or successor order code is on record. Compliance documentation covers EN/IEC 61008-1 and EN/IEC 61008-2-1 for RCCB performance and safety. The 8/20 µs impulse withstand of 3000 A per EN/IEC 61008-1 confirms the unit's immunity to surge currents from lightning or switching transients.

Integration notes

The toggle control and contact position indicator give a clear visual of the mechanical state, and the padlocking device allows lockout/tagout in the off position. Mechanical durability is rated at 20000 cycles; electrical durability under AC-1 resistive load is 10000 cycles. Storage temperature range is -40...85 °C, operating range -25...60 °C — acceptable for most indoor panel environments.

Frequently asked questions

What is the closest alternative to A9Z25480 in the same family?

Within the Acti9 iID range, the closest peer is a 4P RCCB with the same 80 A rating and Type A sensitivity but without the selective time delay — the standard (instantaneous) version. The selective version here coordinates with downstream devices; the standard version trips faster for single-point protection.

MPN
A9Z25480