Schneider Electric A9Z32263 — Residual Current Breakers (RCCB/RCBO)

A9Z32263 Acti9 iID RCCB, 63 A, 100 mA, Type A-SI, 2P

MPNA9Z32263
Obsolete

Schneider Electric Acti9 iID, Residual Current Circuit Breaker (RCCB), 2P, 63 A, 100 mA sensitivity, Type A-SI (Super Immunised), clip-on DIN rail, 10 kA SCCR.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z32263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z32263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z32263 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z32263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73 mm
A9Z32263 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z32263 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The A9Z32263 is a 2-pole (2P) residual current circuit breaker (RCCB) from the Schneider Electric Acti9 iID range, rated 63 A continuous current with a 100 mA earth-leakage sensitivity. The unit clips onto a DIN rail (4 modules wide, 36 mm per the 9 mm pitch count) and fits a standard modular enclosure. Rated operational voltage is 220…240 V AC at 50/60 Hz, with an insulation voltage of 500 V AC and impulse withstand of 6 kV. The breaking capacity is 1500 A (Idm/Im), and the conditional short-circuit current (SCCR) is 10 kA — meaning the device can safely withstand a 10 kA fault upstream without rupturing, provided the upstream overcurrent device is properly coordinated.

Clip-on mounting on a DIN rail, neutral on the left. The housing is IP20 (fingers) and IP40 inside a modular enclosure. A padlocking device is available for lockout/tagout.

The A9Z32263 is listed as current-production (active lifecycle stage).

Frequently asked questions

Where can I buy A9Z32263 and how do I get a price?

The A9Z32263 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is A9Z32263's listed depth (73 mm) on this component line?

The listed depth is 73 mm. The overall dimensions are 91 mm height × 36 mm width (4 modules) × 73 mm depth.

What is A9Z32263's listed range (Acti9) on this component line?

The A9Z32263 belongs to the Schneider Electric Acti9 range, specifically the iID series of residual current circuit breakers.

What compliance documentation does this brand provide for A9Z32263 (RoHS, REACH, UL, IEC)?

The A9Z32263 is certified to EN/IEC 61008-1 and EN/IEC 61008-2-1. It carries IP20 and IP40 ratings per IEC 60529. The evidence does not list RoHS, REACH, or UL marks — verify with the manufacturer for specific documentation.