Skip to main content
Schneider Electric A9Z35280 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z35280 Acti9 iID RCCB, 80 A, 300 mA, 2P

MPNA9Z35280
Obsolete

Schneider Electric Acti9 iID, Residual current circuit breaker (RCCB), 2P, 80 A, 300 mA, Type A-SI, 220-240 V AC, 10 kA.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z35280 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delaySelective
Residual-current tripping technologyVoltage independent
A9Z35280 — Electrical Ratings
ParameterValue
Rated current (In)80 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z35280 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z35280 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73 mm
A9Z35280 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z35280 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9Z35280 is a 2-pole (2P) residual current circuit breaker (RCCB) from the Acti9 iID series, rated for 80 A continuous current at 220-240 V AC, 50/60 Hz. It provides earth-leakage protection with a 300 mA sensitivity and is classified as Type A-SI (Super Immunised), meaning it handles pulsed DC residual currents and is immune to nuisance tripping from high-frequency leakage typical of modern electronic loads. The voltage-independent tripping mechanism operates without an auxiliary supply, so it clears a ground fault even if the line voltage collapses.

The 80 A rating (In) is the continuous current the RCCB can carry without derating in a 30 °C ambient — match it to the load side of your distribution board. The 300 mA sensitivity is a selective (time-delayed) trip threshold, per, which coordinates with downstream 30 mA RCCBs so only the faulted circuit opens, not the whole board. The Type A-SI classification covers sinusoidal AC and pulsating DC residual currents plus a high immunity to surge-induced tripping — important for circuits with VFDs, UPS systems, or switched-mode power supplies that generate leakage at higher frequencies. The breaking and making capacity is 1500 A (Idm/Im per) — sufficient for clearing high-impedance ground faults but not for direct short-circuit interruption; that is the upstream MCB or fuse's job. Electrical durability is rated at 10,000 cycles under AC-1 resistive load, and mechanical durability at 20,000 cycles.

The device occupies 4 module pitches of 9 mm each, so 36 mm total width. Depth is 73 mm, height 91 mm. Neutral is on the left. Terminals accept up to 35 mm² rigid or 25 mm² flexible, with a wire stripping length of 14 mm and a tightening torque of 3.5 N·m. The IP20 body is finger-safe; IP40 with the modular enclosure. A padlocking device and contact position indicator are standard.

Designed and certified to EN/IEC 61008-1 and EN/IEC 61008-2-1 — the harmonized European and international standards for RCCBs. The 8/20 µs impulse withstand of 3000 A confirms surge immunity per the same standard. The Type A-SI classification is a Schneider-specific enhancement over standard Type A, adding super-immunised characteristics for installations with electronic loads.

Frequently asked questions

What is the A9Z35280 used for?

It is a 2-pole residual current circuit breaker (RCCB) providing earth-leakage protection at 300 mA sensitivity, Type A-SI, for 80 A circuits at 220-240 V AC. It is voltage-independent and selective, so it coordinates with downstream 30 mA RCCBs in a distribution board.

What are the key specifications of the A9Z35280?

80 A rated current, 300 mA sensitivity, Type A-SI, 2 poles, 220-240 V AC, 50/60 Hz, 10 kA conditional short-circuit current, 6 kV impulse withstand, 500 V insulation voltage, selective time delay, voltage-independent tripping.

Where can I buy the A9Z35280?

This RCCB is sourced and quoted to order against an RFQ through independent industrial distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

What compliance standards does the A9Z35280 meet?

It is certified to EN/IEC 61008-1 and EN/IEC 61008-2-1, the harmonized standards for residual current circuit breakers. It also carries an 8/20 µs impulse withstand rating of 3000 A per the same standard.

MPN