Skip to main content
Schneider Electric A9Z95463

Schneider Electric A9Z95463

MPNA9Z95463
Obsolete

Residual current circuit breaker (RCCB), Acti9 iID, 4P, 63A, A-SI type, 300mA, selective, double terminal

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9Z95463 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeResidual current circuit breaker (RCCB)
Voltage500 V AC 50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV
Current63 A
Residual current tripping technologyVoltage independent
Rated conditional short-circuit current10 kA
Network frequency50/60 Hz
Poles description4P
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529

All specifications

A9Z95463 additional specifications
ParameterValue
Mounting modeClip-on
Mounting supportDIN rail
Wire stripping length14 mm for top or bottom connection
Connections - terminalsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Pollution degree3
Depth73 mm
Width72 mm
ColorWhite
Height91 mm
Electrical durabilityAC-1: 15000 cycles
Mechanical durability20000 cycles
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1
RangeActi9
9 mm pitches8
Neutral positionLeft
Device short nameiID
Tightening torque3.5 N.m top or bottom
Earth-leakage sensitivity300 mA
Contact position indicatorYes
Locking options descriptionPadlocking device
Electromagnetic compatibility8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1
Earth-leakage protection classType A-SI (Super Immunised)
Rated breaking and making capacityIdm 1500 A Im 1500 A
Ambient air temperature for storage-40...85 °C
Earth-leakage protection time delaySelective
Ambient air temperature for operation-25...60 °C
MPN
A9Z95463