Specifications

ABLS1A48025 key specifications
ParameterValue
Range of productModicon Power Supply
Power supply typeRegulated switch mode
Input protection typeIntegrated fuse (not interchangeable) 4 A External protection (recommended) 20 A Curve C External protection (recommended) 13 A Curve C
Output protection typeAgainst overload and short-circuits, protection technology: automatic reset Against over temperature, protection technology: manual reset Against overvoltage, protection technology: manual reset
Product or component typePower supply
Output voltage48 V DC
Nominal input voltage100...240 V AC single phase 100...240 V AC phase to phase 140...340 V DC
Output voltage adjustment44...56 V
Inrush current30.0 A 115 V 60.0 A 230 V
Current consumption< 2.5 A 115 V AC < 1.4 A 230 V AC < 1.3 A 140 V DC
Maximum leakage current1 mA 240 V AC
Power supply output current2.5 A

All specifications

ABLS1A48025 additional specifications
ParameterValue
Power factor0.55 at 115 V AC 0.45 at 230 V AC
Rated power in120 W
Power dissipation in23 W
Nominal network frequency50...60 Hz
Enclosure materialAluminum
IP degree of protectionIP20
Mounting supportTop hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 Double-profile DIN rail
Connections - terminalsScrew connection 0.5...4 mm², AWG 20...AWG 12) without wire end ferrule output Screw connection 0.5...2.5 mm², AWG 20...AWG 14) with wire end ferrule output Screw connection 0.75...4 mm², AWG 18...AWG 12) without wire end ferrule input Screw connection 0.75...4 mm², AWG 18...AWG 12) with wire end ferrule input
Pollution degree2
Shock resistance150 m/s² 11 ms
Operating altitude< 5000 m
Vibration resistance3 mm (f= 2...9 Hz) conforming to IEC 60068-2-6 10 m/s² (f= 9...200 Hz) conforming to IEC 60068-2-6
Electrical shock protection classClass I
Depth4.6 in (117.6 mm)
Width1.6 in (40 mm)
Height4.9 in (123.6 mm)
Meantime between failure [MTBF]700000 h at 77 °F (25 °C), full load conforming to SR 332
StandardsIEC 62368-1 EN/IEC 61204-3 IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3 IEC 61000-6-4 IEC 61000-3-2 EN 61000-3-3 UL 62368-1 CSA C22.2 No 62368-1 UL 508 CSA C22.2 No. 107.1
SupplySELV IEC 60950-1 SELV IEC 60204-1 SELV IEC 60364-4-41
CategoryUS1CP1222525
Efficiency85 % 115 V AC 88 % 230 V AC
Status LED1 LED (Green) output voltage
Holding time> 20 ms 115 V AC > 40 ms 230 V AC
Service life10 year(s)
Turn-on time< 1 s
Variant optionOptimized
Output couplingParallel
Residual ripple< 150 mV
Dielectric strength3000 V AC with input to output
Overvoltage categoryII
Efficiency at full load85...264 V AC without temperature derating 120...375 V DC without temperature derating
Electromagnetic emissionConducted emissions IEC 61000-6-3 Radiated emissions IEC 61000-6-4
Electromagnetic immunityImmunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2 Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5 Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5 Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Immunity to voltage dips conforming to IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to IEC 61000-3-2 conforming to EN 55016-1-2 conforming to EN 55016-2-1
Line and load regulation< 0.5 % network 0 to 100 % load at 77 °F (25 °C) < 1 % network full voltage range in line at 77 °F (25 °C)
Network system compatibilityTN TT IT
Startup with capacitive loads4000 µF
Ambient air temperature for operation-4...14 °F (-20...-10 °C) with current derating of 2 % per °C mounting position A < 6561.68 ft (2000 m) 14...104 °F (-10...40 °C) without derating mounting position A 115 V AC < 6561.68 ft (2000 m) 14...122 °F (-10...50 °C) without derating mounting position A 230 V AC < 6561.68 ft (2000 m) 104...158 °F (40...70 °C) with current derating of 1.67 % per °C mounting position A 115 V AC < 6561.68 ft (2000 m) 122...158 °F (50...70 °C) with current derating of 2.5 % per °C mounting position A 230 V AC < 6561.68 ft (2000 m)
MPN