Schneider Electric ABLU3A48200
MPNABLU3A48200
Active
Industrial, DIN Rail Power Supplies
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Range of product | Modicon Power Supply |
| Power supply type | Regulated switch mode |
| Input protection type | Integrated fuse (not interchangeable) 3.15 A External protection (recommended) |
| Output protection type | Against overload and short-circuits, protection technology: manual or automatic reset by switch Against over temperature, protection technology: automatic reset Against overvoltage, protection technology: manual reset |
| Product or component type | Power supply |
| Output voltage | 48 V DC |
| Nominal input voltage | 380...500 V AC three phase |
| Output voltage adjustment | 48...56 V |
| Inrush current | 35 A 380 V 35 A 500 V |
| Current consumption | < 1.9 A 380 V AC < 1.7 A 500 V AC |
| Maximum leakage current | 2 mA 500 V AC |
| Power supply output current | 20 A |
All specifications
| Parameter | Value |
|---|---|
| Permissible temporary current boost | 1.5 x In for 5 seconds) |
| Power factor | 0.90 at 380 V AC 0.90 at 500 V AC |
| Rated power in | 960 W |
| Power dissipation in | 49 W |
| Nominal network frequency | 50...60 Hz |
| Enclosure material | Metal |
| IP degree of protection | IP20 |
| Mounting support | Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 Double-profile DIN rail |
| Connections - terminals | Screw connection 4 x 10 mm², AWG 12...AWG 8) with wire end ferrule output Screw connection 4...16 mm², AWG 12...AWG 6) without wire end ferrule output Screw connection 0.75...6 mm², AWG 18...AWG 10) without wire end ferrule input Screw connection 0.75...4 mm², AWG 18...AWG 12) with wire end ferrule input Cage clamp 0.2...1.5 mm², AWG 22...AWG 16) without wire end ferrule diagnostic relay Cage clamp 0.2...1.5 mm², AWG 22...AWG 16) without wire end ferrule shut down input Cage clamp 0.2...0.75 mm², AWG 22...AWG 18) with wire end ferrule diagnostic relay Cage clamp 0.2...0.75 mm², AWG 22...AWG 18) with wire end ferrule shut down input |
| Pollution degree | 2 |
| Shock resistance | 150 m/s² 11 ms |
| Operating altitude | < 5000 m overvoltage category III overvoltage category II |
| Vibration resistance | 3.5 mm (f= 3...11.9 Hz) conforming to IEC 60068-2-6 20 m/s² (f= 11.9...150 Hz) conforming to IEC 60068-2-6 |
| Electrical shock protection class | Class I |
| Depth | 5.07 in (128.7 mm) |
| Width | 4.3 in (110 mm) |
| Height | 4.9 in (124 mm) |
| Meantime between failure [MTBF] | 912400 h at 77 °F (25 °C), full load conforming to SR 332 382500 h at 131 °F (55 °C), 80 % load conforming to SR 332 |
| Standards | IEC 62368-1 EN/IEC 61204-3 IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3 IEC 61000-6-4 IEC 61000-3-2 EN 61000-3-3 UL 62368-1 CSA C22.2 No 62368-1 CSA C22.2 No. 107.1 |
| Supply | SELV IEC 60950-1 SELV IEC 60204-1 SELV IEC 60364-4-41 |
| Marking | CE UKCA |
| Category | US1CP1222524 |
| Efficiency | 95 % 380 V AC 95 % 500 V AC |
| Status LED | 1 LED (green and red) product status |
| Holding time | > 20 ms 380 V AC > 20 ms 500 V AC |
| Service life | 10 year(s) 104 °F (40 °C) 80 % load |
| Turn-on time | < 2 s |
| Shutdown input | Non isolated input, dry contact 0.3 mA 4 V |
| Variant option | Universal |
| Output coupling | Single/parallel by switch |
| Residual ripple | < 200 mV |
| Diagnostic relay | Electromechanical relay 1000.0 mA 30 V |
| Dielectric strength | 4000 V AC with input to output 2000 V AC with input to ground 1500 V AC with output to ground 4000 V AC with input to diagnostic relay 500 V AC with output to diagnostic relay 1500 V AC with diagnostic relay to ground 4000 V AC with shutdown input to input 1500 V AC with shutdown input to ground with shutdown input not isolated from output |
| Overvoltage category | III II |
| Efficiency at full load | 320...575 V AC 3 phase |
| Electromagnetic emission | Conducted emissions IEC 61000-6-3 Radiated emissions IEC 61000-6-4 |
| Electromagnetic immunity | Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2 Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2 Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5 Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5 Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8 Immunity to voltage dips conforming to IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to IEC 61000-3-2 conforming to EN 55016-1-2 conforming to EN 55016-2-1 |
| Line and load regulation | < 0.17 % network 100 % load in line at 77 °F (25 °C) < 0.6 % +/- 0.5 % network 100 % load at 77 °F (25 °C) for single mode 4 % network 150 % load at 77 °F (25 °C) for parallel mode |
| Network system compatibility | TN TT IT |
| Startup with capacitive loads | 200000 µF |
| Ambient air temperature for operation | -13...131 °F (-25...55 °C) without current derating mounting position A < 6561.68 ft (2000 m) 131...158 °F (55...70 °C) with current derating of 3.3 % per °C mounting position A < 6561.68 ft (2000 m) |
MPN
ABLU3A48200