| Apparent power | 2.8 kVA 380 V |
|---|
| Motor power | 1.5 kW |
|---|
| Maximum horse power rating | 2 hp |
|---|
| Supply frequency | 50...60 Hz - 5...5 % |
|---|
| Network frequency | 47.5...63 Hz |
|---|
| Switching frequency | 6...16 kHz adjustable 12...16 kHz with derating factor |
|---|
| Frequency resolution | Display unit 0.1 Hz Analog input 0.024/50 Hz |
|---|
| Nominal switching frequency | 12 kHz |
|---|
| Speed drive output frequency | 0.5...200 Hz |
|---|
| Phases | 3 phase |
|---|
| IP degree of protection | IP55 IEC 61800-5-1 IP55 IEC 60529 |
|---|
| Physical interface | 2-wire RS 485 |
|---|
| Communication service | Monitoring inhibitable Read holding registers (03) 2 words maximum Read device identification (43) Write multiple registers (16) 2 words maximum Time out setting from 0.1 to 100 s Write single register (06) |
|---|
| Communication port protocol | METASYS N2 APOGEE FLN Modbus BACnet LonWorks |
|---|
| EMC filter | Class C2 EMC filter integrated |
|---|
| Pollution degree | 2 IEC 61800-5-1 |
|---|
| Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
|---|
| Relative humidity | 5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3 |
|---|
| Operating altitude | 3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating |
|---|
| Vibration resistance | 1.5 mm (f= 3...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8 |
|---|
| Depth | 7.6 in (192 mm) |
|---|
| Width | 8.5 in (215 mm) |
|---|
| Height | 11.7 in (297 mm) |
|---|
| Standards | IEC 61800-5-1 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 CE UL CSA C-Tick N1831 GOST |
|---|
| Marking | CE |
|---|
| Category | US1CP4D22157 |
|---|
| Data format | 8 bits, 1 stop, odd even or no configurable parity |
|---|
| Noise level | 48 dB 86/188/EEC |
|---|
| Option card | Communication card LonWorks |
|---|
| Speed range | 1...10 |
|---|
| Functionality | Mid |
|---|
| Assembly style | With heat sink |
|---|
| Speed accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
|---|
| Regulation loop | Adjustable PI regulator |
|---|
| Torque accuracy | +/- 15 % |
|---|
| Local signalling | 1 LED (red) for DC bus energized |
|---|
| Device short name | ATV212 |
|---|
| Transmission rate | 9600 bps or 19200 bps |
|---|
| Operating position | Vertical +/- 10 degree |
|---|
| Transmission frame | RTU |
|---|
| Number of addresses | 1...247 |
|---|
| Product destination | Asynchronous motors |
|---|
| Prospective line isc | 5 kA |
|---|
| Specific application | HVAC |
|---|
| Transient overtorque | 120 % of nominal motor torque +/- 10 % 60 s |
|---|
| Analogue input number | 2 |
|---|
| Braking to standstill | By DC injection |
|---|
| Analogue output number | 1 |
|---|
| Discrete output number | 2 |
|---|
| Motor slip compensation | Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load |
|---|
| Environmental characteristic | Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3 |
|---|
| Product specific application | Pumps and fans in HVAC |
|---|
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
|---|
| Asynchronous motor control profile | Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, standard Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio, 2 points |
|---|
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 3200 s Automatic based on the load |
|---|
| Ambient air temperature for storage | -13...158 °F (-25...70 °C) |
|---|
| Ambient air temperature for operation | 14...104 °F (-10...40 °C) (without derating) 104...122 °F (40...50 °C) (with derating factor) |
|---|