Skip to main content
Schneider Electric ATV21HD11M3X — AC Drive (VFD) 240V

Schneider Electric ATV21HD11M3X Altivar 21 VFD, 11 kW

MPNATV21HD11M3X
Obsolete

Schneider Electric Altivar 21 ATV21HD11M3X AC drive, 11 kW, 200-240 V 3-phase, 17.6 kVA, 34.4 A line current, CE, mature lifecycle.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV21HD11M3X — Electrical Output
ParameterValue
Motor power (normal / heavy duty)11 kW
ATV21HD11M3X — Approvals
ParameterValue
Compliance standardsIEC 61800-5-1 IEC 61800-3 environments 1 category C2 UL Type 1 EN 61800-3 environments 1 category C3 IEC 61800-3 environments 1 category C3 EN 61800-5-1 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 IEC 61800-3 environments 2 category C3 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C3
ATV21HD11M3X — Mechanical
ParameterValue
Height13.0 in (329.5 mm)
Width9.6 in (245 mm)

Product details

11 kW VFD for 200-240 V three-phase lines

The ATV21HD11M3X is a 11 kW Altivar 21 variable frequency drive designed for 200-240 V three-phase input, pulling 34.4 A at 240 V and 42.1 A at 200 V line current. Rated apparent power is 17.6 kVA at 240 V, and the drive delivers a transient overtorque of 120% of nominal motor torque for 60 seconds — enough to handle short-duration load spikes on pumps or fans.

Switching frequency and derating

The adjustable switching frequency range is 6-16 kHz, with a derating factor applied above 12 kHz. Running at 16 kHz quiets motor whine but reduces the continuous output current — plan the thermal budget around the derating curve. The drive measures 13.0 x 9.6 x 7.5 inches (329.5 x 245 x 190 mm) and mounts vertically with a heat sink.

Fieldbus and communication options

The drive includes a 2-wire RS-485 physical interface with RTU transmission frame, configurable at 9600 or 19200 bps. Addressing supports 1-247 nodes on the bus. Optional communication cards add APOGEE FLN, BACnet, LonWorks, or METASYS N2 protocols — useful for building management system integration.

Standards and compliance

The ATV21HD11M3X carries CE marking and complies with IEC 61800-5-1 (safety) and IEC 61800-3 (EMC) for environments 1 and 2, categories C1 through C3. The pollution degree is 2 per IEC 61800-5-1. Dielectric strength is 2830 V DC between earth and power terminals, and 4230 V DC between control and power terminals. Operating altitude is limited to 2000 m for corner-grounded distribution networks.

Frequently asked questions

What is ATV21HD11M3X's listed depth?

The ATV21HD11M3X has a depth of 7.5 inches (190 mm). Overall dimensions are 13.0 x 9.6 x 7.5 inches (H x W x D).

What compliance documentation does Schneider Electric provide for ATV21HD11M3X?

The drive is CE marked and complies with IEC 61800-5-1 for safety and IEC 61800-3 for EMC, covering environments 1 and 2 with categories C1 through C3. Pollution degree is 2 per IEC 61800-5-1.

MPN
ATV21HD11M3X