Skip to main content
Schneider Electric ATV930U22N4

Schneider ATV930U22N4 Altivar Process Drive, 2.2kW, 380-480V

MPNATV930U22N4
Active

Schneider Altivar Process ATV930U22N4 variable speed drive, 2.2 kW normal duty, 3-phase 380-480 V, 5.6 A output, with braking chopper.

$533.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

ATV930U22N4 key specifications
ParameterValue
Range of productAltivar Process ATV900
Type of polarizationNo impedance
Product or component typeVariable speed drive
Supply voltage380...480 V
Relative symmetric mains voltage tolerance10 %
Nominal output current5.6 A
Continuous output current5.6 A 4 kHz normal duty 4 A 4 kHz heavy duty
Motor power2.2 kW normal duty 1.5 kW heavy duty
Relative symmetric network frequency tolerance5 %
Phases3 phase
IP ratingUL type 1
IP degree of protectionIP21

All specifications

ATV930U22N4 additional specifications
ParameterValue
Communication port protocolModbus TCP EtherNet/IP Modbus serial
Mounting modeWall mount
Electrical connectionControl screw terminal 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal 2.5...6 mm² AWG 14...AWG 10 Motor screw terminal 2.5...6 mm² AWG 14...AWG 10 DC bus screw terminal 2.5...6 mm² AWG 14...AWG 10
EMC filterIntegrated With EMC plate option
Pollution degree2
Shock resistance15 gn 11 ms IEC 60068-2-27
Relative humidity5...95 % without condensation IEC 60068-2-3
Operating altitude1000...4800 m with current derating 1 % per 100 m
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Permitted relative humidity (during operation)Class 3K5 according to EN 60721-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)10 m/s² at 13...200 Hz
StandardsUL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
SupplyExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm 500 V DC for 1 minute to earth
MarkingCE
VariantStandard version With braking chopper
CategoryUS1CP4E22276
Data format8 bits, configurable odd, even or no parity
Noise level54.5 dB
Maximum THDI<48 % full load IEC 61000-3-12
Exchange modeHalf duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Option moduleSlot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module communication module Ethernet Powerlink
Assembly styleEnclosed
Regulation loopAdjustable PID regulator
Transmission rate10, 100 Mbits 4.8 kbps 9600 bit/s 19200 bit/s
Device applicationIndustrial Application
Operating positionVertical +/- 10 degree
Number of addresses1...247
Product destinationSynchronous motors Asynchronous motors
Overvoltage categoryIII
Volume of cooling air10038.7 Gal/hr(US) (38 m3/h)
Environmental characteristicChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Product specific applicationProcess for industrial
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Ambient air transport temperature-40...158 °F (-40...70 °C)
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
Maximum deflection under vibratory load (during operation)1.5 mm at 2...13 Hz

Product details

The ATV930U22N4 is a 2.2 kW normal duty / 1.5 kW heavy duty variable speed drive from the Altivar Process family. It runs on a 3-phase 380…480 V supply and delivers 5.6 A continuous at 4 kHz. For a heavy-duty constant-torque motor load, the output drops to 4 A at the same switching frequency. Built-in braking chopper handles deceleration without an external resistor for basic profiles — saves a DIN-rail slot and a sourcing line. The drive includes a standard EMC filter (integrated, with an EMC plate option).

Control wiring and supply

Digital inputs need an external 24 V DC (19…30 V). The drive generates its own 24 V for the STO safety function (21…27 V) and a 10.5 V reference for a potentiometer (1…10 kΩ). Keep the STO supply separate if you wire a remote emergency stop. Control connections use screw terminals for 0.5…1.5 mm² (AWG 20…16); power terminals accept 2.5…6 mm² (AWG 14…10). Mount vertically ±10° with cooling air volume 38 m³/h (10038.7 Gal/hr(US)). IP21 and UL Type 1 suit indoor panels.

Standards and lifecycle

If you are stocking a spare for an existing ATV930 line machine, this order code matches the nominal ratings. No end-of-life notice is active, but for reliability-critical assets, keep one in the cabinet — the 1-247 Modbus address range and the half/full-duplex Ethernet IP interface are common across the family, so a swap-in is straightforward.

Frequently asked questions

What is the input phase requirement?

The drive requires a 3-phase supply. The rated voltage is 380…480 V.

What control supply voltages does it need?

Digital inputs need an external 24 V DC (19…30 V). The drive supplies an internal 24 V for STO (21…27 V) and a 10.5 V potentiometer reference.

What compliance certifications does it carry?

UL 508C, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1 are listed. CE marking is standard.

MPN
ATV930U22N4