ATV930U22Y6 key specifications
ParameterValue
Range of productAltivar Process ATV900
Type of polarizationNo impedance
Product or component typeVariable speed drive
Supply voltage500...690 V
Relative symmetric mains voltage tolerance10 %
Nominal output current3.1 A
Continuous output current3.1 A 4 kHz normal duty 2.4 A 4 kHz heavy duty
Motor power1.5 kW normal duty 1.1 kW heavy duty
Relative symmetric network frequency tolerance5 %
Phases3 phase
IP ratingUL type 1
IP degree of protectionIP21

All specifications

ATV930U22Y6 additional specifications
ParameterValue
Communication port protocolEtherNet/IP Modbus serial Modbus TCP
Mounting modeWall mount
Electrical connectionControl screw terminal 0.5...1.5 mm² AWG 20...AWG 16 DC bus screw terminal 4...10 mm² AWG 12...AWG 8 Line side screw terminal 4...10 mm² AWG 12...AWG 8 Motor screw terminal 4...10 mm² AWG 12...AWG 8
EMC filterIntegrated With EMC plate option
Pollution degree2
Shock resistance15 gn 11 ms IEC 60068-2-27
Relative humidity5...95 % without condensation IEC 60068-2-3
Operating altitude1000...4800 m with current derating 1 % per 100 m
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Permitted relative humidity (during operation)Class 3K5 according to EN 60721-3
Maximum acceleration under shock impact (during operation)150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)10 m/s² at 13...200 Hz
StandardsUL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
SupplyExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm 500 V DC for 1 minute to earth
MarkingCE
VariantStandard version With braking chopper
CategoryUS1CP4E22276
Data format8 bits, configurable odd, even or no parity
Noise level58 dB
Exchange modeHalf duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Option moduleSlot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module communication module Ethernet Powerlink
Assembly styleEnclosed
Regulation loopAdjustable PID regulator
Transmission rate10, 100 Mbits 4.8 kbps 9600 bit/s 19200 bit/s
Device applicationIndustrial Application
Operating positionVertical +/- 10 degree
Number of addresses1...247
Product destinationSynchronous motors Asynchronous motors
Overvoltage categoryIII
Volume of cooling air87178.3 Gal/hr(US) (330 m3/h)
Environmental characteristicChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
Product specific applicationProcess for industrial
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Ambient air transport temperature-40...158 °F (-40...70 °C)
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)
Environmental class (during operation)Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
Maximum deflection under vibratory load (during operation)1.5 mm at 2...13 Hz

Product details

Drive identity and fit

The ATV930U22Y6 is a standard-variant Altivar Process ATV900 variable speed drive with an integrated braking chopper. It operates on a 500-690 V three-phase supply and is rated for 1.5 kW normal duty or 1.1 kW heavy duty (continuous output current 3.1 A at 4 kHz normal duty, 2.4 A at 4 kHz heavy duty). Built-in EMC filter and IP21 / UL Type 1 enclosure keep it panel-ready for most industrial environments.

Compliance and marking

CE marked, UL 508C listed, and designed to IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), plus functional safety standards IEC 61508 and IEC 13849-1. Documentation for RoHS/REACH is standard for the brand — the compliance pack is what you'd expect for a drive sold globally.

Supply and control wiring

Digital inputs need an external 24 V DC supply (19-30 V). The drive internally provides 10.5 V DC for a 1-10 kΩ potentiometer and a separate 24 V DC for digital inputs and STO (21-27 V). Control terminals accept 0.5-1.5 mm². Line and motor terminals accept 4-10 mm². Communication options include Ethernet/IP, Modbus TCP, and Modbus serial; slots A, B, C accept optional modules for Profibus, PROFINET, EtherCAT, CANopen, I/O extensions, and encoder interfaces.

Frequently asked questions

What is the phase configuration of the ATV930U22Y6?

It is a three-phase drive, operating from a 500-690 V three-phase supply.

What supply voltages does the ATV930U22Y6 require for its control circuitry?

The drive needs an external 24 V DC supply (19-30 V) for digital inputs. It also provides an internal 10.5 V DC reference for a potentiometer (1-10 kΩ) and a separate 24 V DC supply (21-27 V) for digital inputs and STO.

What compliance standards does the ATV930U22Y6 meet?

It is CE-marked and UL 508C listed, and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.