Skip to main content
Schneider Electric ATV960C35T4X1

Schneider Electric ATV960C35T4X1

MPNATV960C35T4X1
Active

Variable speed drive, Altivar Process ATV900, High Performance System ATV960, 400/315 kW, 480 V, IP23

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

ATV960C35T4X1 key specifications
ParameterValue
Type of coolingForced convection
Range of productAltivar Process ATV900
Product or component typeVariable speed drive
Output voltage1 MOhm 500 V DC for 1 minute to earth
Supply voltage480 V +/- 10 %
Supply frequency50/60 Hz +/- 5 %
Network number of phases3 phases
Colour of enclosureLight grey (RAL 7035)
IP degree of protectionIP23 conforming to IEC 61800-5-1
Communication port protocolEtherNet/IP Modbus TCP Modbus serial
Pollution degree2 conforming to IEC 61800-5-1
Shock resistance4 gn for 11 ms conforming to IEC 60068-2-27 3M2 conforming to IEC 60721-3-3

All specifications

ATV960C35T4X1 additional specifications
ParameterValue
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Operating altitude< 1000 m without derating 1000...2000 m with current derating 1 % per 100 m 2000...3800 m with current derating 1 % per 100 m for TT earthing system 2000...3800 m with current derating 1 % per 100 m for TN earthing system 2000...3800 m with current derating 1 % per 100 m for IT earthing system 3800...4800 m with current derating 1 % per 100 m for TT earthing system 3800...4800 m with current derating 1 % per 100 m for TN earthing system
Vibration resistance1.5 mm peak to peak (f= 3...10 Hz) conforming to IEC 60068-2-6 0.6 gn (f= 10...200 Hz) conforming to IEC 60068-2-6 3M3 conforming to IEC 60721-3-3
StandardsIEC 60204-1 IEC 61800-2 IEC 61800-3 IEC 61800-5-1
MarkingCE
Maximum THDI<48 % full load conforming to IEC 61000-3-12
Assembly styleIn floor-standing enclosure compact version
Device short nameATV960
Operating positionVertical +/- 10 degree
Provided equipmentEnclosure PanelSeT SFN Graphical operating panel in the enclosure door Frequency inverter Main switch Line choke Terminal block main supply Terminal block motor
Product destinationAsynchronous motors Synchronous motors
Overvoltage categoryIII
Environmental characteristicChemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 Humidity resistant class 3K3 conforming to IEC 60721-3-3
Electromagnetic compatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Ambient air temperature for storage-25...70 °C
Ambient air temperature for operation-10...0 °C without derating (with option enclosure heating) 0...40 °C without derating 40...50 °C with derating factor
MPN