The Schneider Modicon X80 BMEAHI0812H is an 8-channel analog input module handling 4–20 mA current loops with built-in HART communication and per-channel broken wire detection. The point-to-point topology keeps each field device on its own dedicated return path, so a fault on one loop stays electrically isolated from the others. Broken wire detection flags an open circuit before the controller sees a saturated or erratic value — useful for catching a cut cable or a failed transmitter before it causes a process excursion. Channel-to-channel isolation is rated at 1000 V DC for 60 seconds; isolation to ground and the backplane bus is even higher at 1400 V DC. A transient on one input will not propagate to its neighbors. Compliance covers UL 61010-2-201, CSA C22.2 No 61010-2-201, IEC 61010-2-201, and ATEX directive 2014/34/EU. It also carries marine type approval per IACS and substation EMC per IEC 61850-3.
Schneider BMEAHI0812H Modicon X80 8-Ch HART AI Module
MPNBMEAHI0812H
Active
Schneider Modicon X80 analog input module, BMEAHI0812H, 8 channels 4–20 mA HART with broken wire detection and conformal coating.
$957.58Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Range of product | Modicon X80 |
| Analogue input type | Current 4...20 mA |
| Product or component type | Analog input module |
| Isolation voltage | 1000 V DC for 60 s between channels 1400 V DC for 60 s between channels and ground 1400 V DC for 60 s between channels and bus |
| Electrical connection | 20 ways terminal block Telefast |
| Operating altitude | 0...2000 m 2000...5000 m with derating factor |
| Standards | IEC 61131-2 IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 IEC 61000-6-5, interface type 1 and type 2 IEC 61850-3, location G IEC 60079-0 |
| Checks | Broken wire detection |
| Topology | Point-to-point |
| Directives | 2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive |
| Input impedance | 250 Ohm internally protective resistor (3.6 to 50 Ohm) |
| Measurement error | 0.15 % of full scale 25 °C 0.55 % of full scale - 25...70 °C |
All specifications
| Parameter | Value |
|---|---|
| Temperature drift | 50 ppm/°C |
| Function available | I/O mapping |
| Protective treatment | Conformal coating |
| Analogue input number | 8 |
| Application specific i (O) | HART |
| Analogue input resolution | 15 bits + sign |
| Isolation between channels | Isolated |
| Environmental characteristic | Gas resistant class Gx conforming to ISA S71.04 Gas resistant class 3C4 conforming to IEC 60721-3-3 Dust resistant class 3S4 conforming to IEC 60721-3-3 Sand resistant class 3S4 conforming to IEC 60721-3-3 Salt resistant level 2 conforming to IEC 68252 Mold growth resistant class 3B2 conforming to IEC 60721-3-3 Fungal spore resistant class 3B2 conforming to IEC 60721-3-3 Hazardous location class I division 2 |
| Ambient air temperature for storage | -40...85 °C |
| Ambient air temperature for operation | -25...70 °C |
Product details
Frequently asked questions
Does this module support broken wire detection?
Yes, the module checks each analog input for an open circuit and flags it, enabling early detection of a failed transmitter or damaged cable.
What is the topology of the BMEAHI0812H?
The module uses point-to-point topology, meaning each channel has its own dedicated return path.
What compliance certifications does the BMEAHI0812H carry?
It complies with IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS, IEC 61850-3, and ATEX (2014/34/EU).
MPN