Skip to main content
Schneider Electric BMEAHO0412C

BMEAHO0412C Modicon X80 Analog Output, 4 Ch 4-20mA HART

MPNBMEAHO0412C
Active

Schneider Modicon X80 analog output module, 4 channels 4-20 mA with HART, 15-bit resolution, isolated channels, conformal coated.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

BMEAHO0412C key specifications
ParameterValue
Range of productModicon X80
Analogue output typeCurrent: 4...20 mA
Product or component typeAnalog output module
Isolation voltage1000 V DC for 60 s between channels 1400 V DC for 60 s between channels and ground 1400 V DC for 60 s between channels and bus
Electrical connection20 ways terminal block Telefast
Operating altitude0...2000 m 2000...5000 m with derating factor
StandardsIEC 61131-2 IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 IEC 61000-6-5, interface type 1 and type 2 IEC 61850-3, location G IEC 60079-0
ChecksBroken wire detection
TopologyPoint-to-point
Directives2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive
Measurement error0.1 % of full scale 25 °C 0.45 % of full scale - 25...60 °C
Temperature drift45 ppm/°C

All specifications

BMEAHO0412C additional specifications
ParameterValue
Function availableI/O mapping
Load impedance ohmic600 Ohm 0...20 mA 570 Ohm 0...21 mA
Protective treatmentConformal coating
Analogue output number4
Application specific i (O)HART
Analogue output resolution15 bits + sign
Isolation between channelsIsolated
Environmental characteristicGas resistant class Gx conforming to ISA S71.04 Gas resistant class 3C4 conforming to IEC 60721-3-3 Dust resistant class 3S4 conforming to IEC 60721-3-3 Sand resistant class 3S4 conforming to IEC 60721-3-3 Salt resistant level 2 conforming to IEC 68252 Mold growth resistant class 3B2 conforming to IEC 60721-3-3 Fungal spore resistant class 3B2 conforming to IEC 60721-3-3 Hazardous location class I division 2
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...60 °C

Product details

Isolation and environment

The BMEAHO0412C: Channels are isolated from each other at 1000 V DC and from ground and the bus at 1400 V DC — you can drive separate loops without common-mode headaches. The module carries conformal coating and is rated for gas (Gx, 3C4), dust (3S4), salt (level 2), and mold (3B2) resistance per ISA and IEC. It also holds Class I Division 2 hazardous location approval.

The module includes broken wire detection and supports point-to-point topology. It complies with IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS, and IEC 61850-3 (location G). ATEX directive 2014/34/EU is covered.

Termination is via a 20-way Telefast terminal block. Load impedance is 600 Ω for 0-20 mA range (570 Ω for 0-21 mA). Temperature drift is 45 ppm/°C.

Frequently asked questions

What compliance documentation is available for this module?

The module carries IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS, and IEC 61850-3 (location G) standards. It also meets the ATEX directive 2014/34/EU for explosive atmospheres.

What are the key ratings of the BMEAHO0412C?

4 channels of 4-20 mA output with HART, 15-bit resolution plus sign, channel isolation 1000 V DC, isolation to ground/bus 1400 V DC, accuracy 0.1% FS at 25 °C, operating temperature -25 to 60 °C.

What environmental protections does this module have?

Conformal coating; gas resistance class Gx (ISA S71.04) and 3C4 (IEC 60721-3-3); dust and sand resistance 3S4; salt resistance level 2; mold and fungal spore resistance 3B2. Also rated for Class I Division 2 hazardous locations.

MPN
BMEAHO0412C