Skip to main content
Schneider Electric C080N45AFM — Miniature Circuit Breakers (MCB)

C080N45AFM ComPacT NS 800A 4P MCCB, MicroLogic 5.0 A, 50 kA

MPNC080N45AFM
Active

Schneider Electric ComPacT NS new generation, C080N45AFM, 800 A at 50 °C, 4P, MicroLogic 5.0 A electronic trip unit, 50 kA Icu at 415 V AC, manually operated, fixed mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080N45AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C080N45AFM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C080N45AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C080N45AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C080N45AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C080N45AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C080N45AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C080N45AFM is a Schneider Electric ComPacT NS new generation moulded-case circuit breaker (MCCB) — a 4-pole, 800 A frame with a MicroLogic 5.0 A electronic trip unit. It is rated 800 A at 50 °C, meaning that at an ambient of 50 °C the breaker carries full rated current without derating; above that temperature you follow the manufacturer's thermal curve. The MicroLogic 5.0 A provides LSI protection: long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I), so it handles both thermal and magnetic trip coordination in a single electronic package.

This breaker is a fixed-mount unit for backplate installation, not a plug-in or draw-out — so it bolts directly into the switchgear. Front connection both upside and downside simplifies busbar or cable routing. IP40 keeps out tools and small debris but is not washdown-rated — indoor panel only. The LCD display shows real-time current readings from the ammeter measurement, useful for load monitoring without a separate meter.

The 15 W power losses are the heat the breaker dissipates at rated current — factor that into panel thermal calculations.

Frequently asked questions

What is C080N45AFM's breaking capacity at 415 V AC?

The C080N45AFM has a breaking capacity of 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What trip unit does the C080N45AFM use?

It uses a MicroLogic 5.0 A electronic trip unit providing LSI protection: long-time overload, short-time short-circuit, and instantaneous short-circuit protection.

Where can I buy C080N45AFM and how is it quoted?

The C080N45AFM is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C080N45AFM