Skip to main content
Schneider Electric C100H32EFM — Miniature Circuit Breakers (MCB)

Schneider C100H32EFM ComPacT NS 3-pole 1000 A MCCB, 85 kA ICu

MPNC100H32EFM
Active

Schneider C100H32EFM Compact Ns New Generation — now discontinued, supplied from remaining surplus and broker stock.

$2,654.10Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

C100H32EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C100H32EFM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C100H32EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C100H32EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100H32EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C100H32EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C100H32EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

Overview

The C100H32EFM is a Schneider ComPacT NS new generation 3-pole molded case circuit breaker rated 1000 A at 50 °C with an 85 kA ICu breaking capacity at 690 V AC, fitted with a MicroLogic 2.0 E electronic trip unit providing L (long-time) and I (instantaneous) protection. It includes an LCD display and integrated energy meter, and is manually operated with a fixed mount and front connection surface.

Rated 1000 A continuous at 50 °C with an 85 kA ICu, this breaker is sized for high-fault distribution panels where the available fault current reaches 85 kA at 690 V AC — typical for industrial main feeders or large sub-distribution. The MicroLogic 2.0 E trip unit covers overload (L) and short-circuit (I) only; no ground-fault or selective protection is built in, so it suits radial distribution rather than zone-selective interlocking.

Compared to the C160H32EFM, the C100H32EFM shares the same 3-pole frame and 85 kA ICu but is rated 1000 A versus 1600 A — pick the C160H32EFM when the load exceeds 1000 A or the BOM specifies a 1600 A frame.

MPN