Schneider Electric C100H35AFM — Miniature Circuit Breakers (MCB)

C100H35AFM ComPacT NS 1000A 3P MCCB, 70kA 415V

MPNC100H35AFM
Active

Schneider Electric ComPacT NS new generation, C100H35AFM, manually operated 3-pole MCCB with MicroLogic 5.0 A electronic trip unit, rated 1000 A, 70 kA Icu at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100H35AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C100H35AFM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C100H35AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C100H35AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100H35AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C100H35AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C100H35AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C100H35AFM is a Schneider Electric ComPacT NS new generation 3-pole moulded-case circuit breaker with a MicroLogic 5.0 A electronic trip unit rated 1000 A at 50 °C. This is the main distribution breaker for a 1000 A bus — not a feeder device. The 70 kA Icu at 415 V AC (breaking capacity code H) means it can safely interrupt a fault current up to 70,000 A at that voltage without self-destructing, which covers most industrial secondary-distribution scenarios on 400 V class systems. The IEC 60947-2 Category B utilisation confirms it is listed for selectivity with downstream breakers, so you can coordinate trips and keep the rest of the plant live when a feeder faults. The electronic trip unit provides LSI protection: long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I). The 20-minute thermal memory means the trip curve remembers prior heating — important for motor-start or repeated inrush loads where a cold-trip calculation would mis-coordinate. The LCD display and ammeter measurement let you read load current on the face without a clamp meter, which speeds troubleshooting on a live panel.

Fixed-mount on a backplate, 327 mm high × 210 mm wide × 147 mm deep. Front-connect both sides — upside and downside — so it fits a typical switchboard lineup without rear-access cable boxes. IP40 front face keeps fingers out; IK07 impact rating handles accidental tool contact in a live panel. Pollution degree 3 (IEC 60947) means it is rated for conductive-dust environments like cement or grain handling, not just clean switchrooms. Power loss is 22 W at rated current — negligible for enclosure heating calculations but worth noting if you pack multiple breakers in a small cabinet. The 4 red fault LEDs and one yellow overload LED give immediate visual status without opening the door.

Frequently asked questions

What is the breaking capacity of C100H35AFM at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it is 65 kA; at 690 V it is 42 kA.

Where can I buy C100H35AFM and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What standards does the C100H35AFM comply with?

Designed and tested to EN/IEC 60947-2, overvoltage category III, pollution degree 3. IP40 and IK07 per IEC 60529 and EN 50102.

What does the MicroLogic 5.0 A trip unit protect against?

LSI protection: long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I). No earth-leakage protection on this variant.