Schneider Electric C100N42AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C100N42AFM ComPacT NS, 1000 A, 4P, MicroL

MPNC100N42AFM
Active

Schneider Electric ComPacT NS new generation, C100N42AFM, 1000 A at 50 °C, 4 poles, MicroLogic 2.0 A electronic trip unit, 85 kA Icu at 220/240 V AC, IP40, fixed mounting.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100N42AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C100N42AFM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C100N42AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C100N42AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100N42AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C100N42AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C100N42AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The C100N42AFM is a fixed-mounted, manually operated 4-pole air circuit breaker from the ComPacT NS new generation family, rated 1000 A at 50 °C. Its MicroLogic 2.0 A electronic trip unit provides L (long-time overload) and I (instantaneous short-circuit) protection — no ground-fault or short-delay element, so selectivity studies need to account for that. The 85 kA Icu at 220/240 V AC (50 kA at 415 V AC) means it can interrupt fault currents up to that level without failing; for a 1000 A main breaker in a 480 V distribution panel, the 50 kA at 415 V AC is the figure to coordinate upstream. The breaker is Category B (IEC 60947-2), meaning it is intended for distribution and has a rated short-time withstand current — it can pass through a delayed trip without damage.

Integration and deployment

Mounts fixed to a backplate — not DIN-rail — so plan for a dedicated panel cutout. Dimensions are 327 mm high × 280 mm wide × 147 mm deep, with a 70 mm connection pitch. The LCD display and ammeter measurement give local current readout without an external meter. IP40 protection means it is suited for indoor switchgear enclosures; IK07 impact resistance handles incidental contact during maintenance.

Frequently asked questions

Where can I buy C100N42AFM and how do I get a price?

The C100N42AFM is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is C100N42AFM's breaking capacity at 415 V AC?

The C100N42AFM has a breaking capacity of 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What protection functions does the MicroLogic 2.0 A trip unit provide?

The MicroLogic 2.0 A provides L (long-time overload) and I (instantaneous short-circuit) protection — no ground-fault or short-delay element.

MPN