Skip to main content
Schneider Electric C100N460FM — Residual Current Breakers (RCCB/RCBO)

C100N460FM ComPacT NS Circuit Breaker, 1000 A, 85 kA Icu

MPNC100N460FM
Active

Schneider Electric ComPacT NS new generation, C100N460FM, 4P fixed circuit breaker, 1000 A, MicroLogic 6.0 electronic trip unit, 85 kA Icu at 240 V AC, 50 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100N460FM — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100N460FM — Electrical Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Number of poles4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Overvoltage categoryIII
Electrical durability2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (operating cycles)10000 cycles
C100N460FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product / component typeCircuit breaker
Product range / familyComPacT
C100N460FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C100N460FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C100N460FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C100N460FM is a Schneider Electric ComPacT NS new generation 4-pole fixed circuit breaker, rated 1000 A at 50 °C, with a MicroLogic 6.0 electronic trip unit providing L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. The 85 kA Icu at 240 V AC and 50 kA at 415 V AC mean this breaker can safely interrupt fault currents up to those levels without upstream coordination failure; the N breaking capacity code (50 kA at 415 V) tells you it's rated for high-fault industrial networks. The 1000 A frame and trip unit are matched, so you don't need to oversize the breaker for the load — it's already sized for a 1000 A feeder or main.

Trip unit and protection logic

MicroLogic 6.0 is an electronic trip unit with a 20-minute thermal memory. That memory means the breaker remembers prior heating from overloads and shortens the trip time on a repeated event — important for motor or transformer feeders where inrush can mask a developing fault. The L, S, I, G protection curves are adjustable via the trip unit's dials, giving you selectivity coordination downstream. No integral earth-leakage protection is included; if you need that, you add an external Vigi module.

Fixed mounting on a backplate, with front connections both upside and downside. Neutral is on the left. Dimensions: 280 mm wide, 327 mm high, 147 mm deep. IK07 impact rating handles accidental tool strikes during installation.

Local signalling and diagnostics

Four red LEDs for fault indication (trip cause) and one yellow LED for overload pre-alarm. That saves time on troubleshooting — you can read the trip history without plugging in a laptop. The manually operated control type means no motor operator is built in; add one externally if remote switching is needed.

Frequently asked questions

How do I get current pricing and availability for C100N460FM?

Submit an RFQ through this listing. The part is sourced and quoted to order through independent distribution; availability and current pricing are confirmed at quote time. No stock count or price is published here.

What is the closest alternative to C100N460FM in the ComPacT family?

Within the ComPacT NS new generation range, the closest alternative would be a breaker with the same 1000 A frame and MicroLogic 6.0 trip unit but a different breaking capacity code (e.g., S or H) if your fault level is lower or higher than the N code's 50 kA at 415 V. The physical footprint and connection pitch are identical across the range, so swapping the breaking capacity code is a direct mechanical fit. Verify the Icu requirement against your system's prospective fault current before substituting.

What compliance documentation does Schneider Electric provide for C100N460FM?

The breaker is certified to EN/IEC 60947-2. It carries an IK07 impact rating per EN 50102 and IP40 per IEC 60529. Pollution degree 3 per IEC 60947 and overvoltage category III are declared. Schneider typically provides a Declaration of Performance and CE marking for this range; RoHS/REACH declarations are available on request from the manufacturer.

MPN
C100N460FM