Generator-duty trip unit, 80 A
The C103MG080 is a TM-G thermal-magnetic trip unit from the ComPacT NSX100...250 family, rated 80 A at 40 °C and built to EN/IEC 60947-2. It is the generator-protection variant — the 'G' suffix means the magnetic trip curve is shaped for the inrush and fault characteristics of generator feeds, not standard distribution loads. Three poles protected (3D), fixed mount, no earth-leakage module.
Long-time pickup (Ir) is adjustable from 0.7 to 1.0 x In (56–80 A), so you can dial it down to match a slightly smaller generator nameplate. The instantaneous magnetic trip is fixed at 200 A, which on a generator circuit avoids nuisance tripping on the higher magnetizing inrush typical of generator step-up transformers.
Panel and integration notes
Fits the ComPacT NSX100...250 fixed-mount breaker frame. Three-pole, 3D protected poles — all three poles have thermal and magnetic elements. IP40 front face.