Skip to main content
Schneider Electric C103MG100 — Miniature Circuit Breakers (MCB)

C103MG100 TM-G Trip Unit, 100 A, 3P, ComPacT NSX

MPNC103MG100
Active

Schneider Electric ComPacT NSX series, TM-G thermal-magnetic trip unit, C103MG100, 100 A rating at 40 °C, 3 poles 3d, 690 V AC / 750 V DC.

$86.27Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C103MG100 — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250 ComPacT NSX100...250 DC
Product/component typeTrip unit
Device applicationGenerator
C103MG100 — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C103MG100 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C103MG100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C103MG100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C103MG100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C103MG100 is a TM-G thermal-magnetic trip unit for the ComPacT NSX100…250 and NSX100…250 DC breaker frames. It carries a 100 A rating at 40 °C and protects three poles with 3d protection. The 690 V AC / 750 V DC rated operational voltage means it handles both AC and DC networks — the DC ceiling is what matters for battery banks or DC bus distribution, where standard AC-only trip units would not coordinate. The LI protection profile gives thermal overload (L) with an adjustable long-time pickup Ir from 0.7 to 1 x In and a fixed long-time delay Tr of 120–400 s at 1.5 x In. The magnetic short-circuit (I) pickup is fixed at 320 A. For a generator application this fixed magnetic threshold means the breaker will not nuisance-trip on generator inrush if the peak is under 320 A — verify against your generator subtransient reactance before committing the BOM line.

The IP40 enclosure rating keeps tools and fingers out but is not washdown-rated; mount inside a panel with a higher-rated door.

Integration notes

The trip unit mounts fixed into the ComPacT NSX breaker — no separate DIN-rail footprint; it is integral to the breaker chassis. The 3P / 3D pole configuration means all three poles are protected, and the trip unit itself is a thermal-magnetic drop-in for the NSX100/160/250 frame. No earth-leakage module is included; if ground-fault protection is required, specify a separate Vigi add-on or choose a different trip unit variant. Network frequency is 50/60 Hz, so it works on either 50 Hz or 60 Hz systems without adjustment.

Frequently asked questions

Where can I buy C103MG100 and how do I get a price?

The C103MG100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time commitment.

What is C103MG100's listed range (ComPacT) on this component line?

The C103MG100 belongs to the ComPacT range, specifically the ComPacT NSX100…250 and NSX100…250 DC product families. It is a trip unit, not a complete breaker — it installs into the NSX breaker frame.

What is C103MG100's listed standards (EN/IEC 60947-2) on this component line?

The C103MG100 is certified to EN/IEC 60947-2, the international standard for low-voltage circuit breakers. This standard covers construction, performance, and test requirements for industrial applications.

MPN