The fixed instantaneous pickup at 320 A (3.2 x In) means the magnetic trip will clear a short-circuit fault above that level; for generator feeds where inrush is lower than motor starting, this fixed band is usually adequate. The 4D protected poles (neutral fully protected at 1 x Ir) suit 4-wire generator outputs where the neutral carries load current and must be treated as a phase.
Schneider Electric C104MG100 TM100G Trip Unit, 100 A, 4P, Ge
Schneider Electric ComPacT NSX series, TM100G trip unit, 4 poles 4D, 100 A, thermal-magnetic, generator application, EN/IEC 60947-2.
Specifications
| Parameter | Value |
|---|---|
| Product range | ComPacT |
| Product range (series) | ComPacT NSX100...250 ComPacT NSX100...250 DC |
| Product/component type | Trip unit |
| Device application | Generator |
| Parameter | Value |
|---|---|
| Poles configuration | 4P |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz 750 V DC |
| Network type (AC/DC) | AC DC |
| Network frequency | 50/60 Hz |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60947-1 |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
What are the key ratings of C104MG100?
The C104MG100 is a 100 A thermal-magnetic trip unit at 40 °C, with 4 protected poles (4D), fixed instantaneous pickup at 320 A, adjustable long-time pickup from 0.7 to 1 x In, and rated for 690 V AC / 750 V DC networks.
Where can I buy C104MG100?
The C104MG100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What standards does C104MG100 comply with?
The C104MG100 complies with EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear, covering circuit-breaker coordination and selectivity.
What is C104MG100 used for?
The C104MG100 is a trip unit for generator applications, providing LI protection (thermal overload and short-circuit) in ComPacT NSX100...250 circuit breakers on AC or DC networks.