Schneider Electric ComPacT NSX, NSX100B, circuit breaker, 16A, TM-D trip unit, 3P, 25 kA Icu at 415 V AC, EN/IEC 60947-2.

$156.87 – $389.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B3TM016 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B3TM016 — Ratings
ParameterValue
Rated current (In)16 A at 40 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B3TM016 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B3TM016 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B3TM016 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B3TM016 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B3TM016 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10B3TM016 is a ComPacT NSX100B moulded-case circuit breaker with a 16 A thermal-magnetic TM-D trip unit, three poles, and a B-frame breaking capacity of 25 kA Icu at 415 V AC. Rated to EN/IEC 60947-2, it is designed for distribution in panelboards and switchboards where the 16 A rating protects branch circuits feeding motor starters, lighting, or small power loads. The 105 mm width and 161 mm height fit standard backplate mounting, with front-facing connections that keep wiring accessible in a multi-breaker lineup.

At 240 V AC the rating climbs to 40 kA Icu. The breaker is category A (no intentional short-time delay), so it trips instantaneously on magnetic pickup; selectivity with downstream MCBs relies on the TM-D curve's magnetic threshold.

Front-facing line and load connections simplify wiring in a multi-row panel; the toggle handle protrudes 86 mm from the mounting surface. IP40 front face keeps tools and fingers out; IK07 impact rating handles accidental tool drops during commissioning.

Thermal-magnetic protection and durability

The TM-D trip unit combines a thermal bimetal for overload protection (L protection) and a magnetic coil for short-circuit protection (I protection). Power dissipation is 2.92 W per pole, so a three-pole breaker dumps about 8.8 W into the enclosure; for a dense lineup, factor that into your thermal budget. Mechanical durability is 50,000 operations; electrical durability at 440 V In is 30,000 cycles, which covers frequent switching in a motor-control centre.

Frequently asked questions

Where can I buy C10B3TM016 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C10B3TM016 at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 240 V it is 40 kA Icu.

What standards does C10B3TM016 comply with?

EN/IEC 60947-2. It is suitable for isolation per that standard and carries pollution degree 3, overvoltage category III, and IP40 protection.