Skip to main content
Schneider Electric C10B3TM025 — Miniature Circuit Breakers (MCB)

Schneider C10B3TM025 ComPacT NSX100B MCCB, 25 A, 25 kA at 41

MPNC10B3TM025
Active

Schneider Electric ComPacT NSX NSX100B, 3-pole MCCB, 25 A TM-D trip unit, 25 kA Icu at 415 V AC, IP40, backplate mount.

$124.98Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10B3TM025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B3TM025 — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration3P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B3TM025 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B3TM025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10B3TM025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B3TM025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B3TM025 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10B3TM025 is a Schneider Electric ComPacT NSX100B moulded-case circuit breaker — 3-pole, 25 A frame, fitted with a TM-D thermal-magnetic trip unit. The 25 kA Icu at 380/415 V AC is the interrupting capacity you coordinate downstream — it clears a fault up to that level without welding contacts or rupturing the case, per IEC 60947-2. Pollution degree 3 means it tolerates conductive pollution in a control-panel environment — no special sealing needed for the typical industrial enclosure.

Mounts flat on a backplate in horizontal or vertical orientation. Front connections on both line and load sides keep wiring accessible inside the enclosure. The 105 mm width and 161 mm height fit standard MCCB panel cutouts; the 86 mm depth leaves room for rear busbar or cable routing. Rated for isolation per EN/IEC 60947-2 — you can use it as a visible-break disconnect for downstream maintenance, provided the handle padlocks in the OFF position.

Frequently asked questions

What is the breaking capacity of C10B3TM025 at 415 V?

25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The same breaker also carries 40 kA at 220/240 V and 20 kA at 440 V.

Can C10B3TM025 be used as a disconnect switch?

Yes, it is suitability for isolation marked per EN/IEC 60947-2. The toggle handle provides visible indication of contact position.

Where can I buy C10B3TM025?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN