Skip to main content
Schneider Electric C10F4

Schneider Electric C10F4

MPNC10F4
Active

Circuit breaker basic frame, ComPacT NSX100F, 36kA at 415VAC 50/60 Hz, 100A, without trip unit, 4 poles

$128.22 – $225.26Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

C10F4 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeWithout protection
Product or component typeBasic frame
Voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508 25 kA at 480 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Current100 A at 40 °C
Breaking capacity codeF 36 kA 415 V AC
[Ics] rated service breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz

All specifications

C10F4 additional specifications
ParameterValue
Poles description4P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Electrical shock protection classClass II on front face
Depth86 mm
Width140 mm
Height161 mm
Electrical durability10000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 20000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability50000 cycles conforming to IEC 60947-2
StandardsEN/IEC 60947-2 UL 60947-4-1
RangeComPacT
Neutral positionLeft
Device short nameNSX100F
Device applicationDistribution
Overvoltage categoryIII
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
MPN
C10F4