Skip to main content
Schneider Electric C10F4TM016C — Molded Case Circuit Breakers (MCCB)

Schneider C10F4TM016C ComPacT NSX100F MCCB, 16A 4P 36kA

MPNC10F4TM016C
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 16 A, 4P, 36 kA at 415 V AC, TM-D trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM016C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM016C — Electrical
ParameterValue
[In] rated current16 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM016C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10F4TM016C is a ComPacT NSX100F moulded-case circuit breaker (MCCB) with a 16 A thermal-magnetic TM-D trip unit, 4 poles, and an F breaking capacity code — 36 kA Icu at 415 V AC. It is designed for distribution applications per EN/IEC 60947-2, with suitability for isolation (yes, per that standard). The 16 A rating at 50 °C means this is the continuous current it handles without nuisance tripping in a warm panel; the thermal element protects against overload (L), the magnetic element against short-circuit (I). For selectivity coordination downstream, that figure gives you headroom to size upstream breakers. At 220/240 V AC the interrupting rating jumps to 85 kA Icu, so it handles high-fault locations like a step-down transformer secondary.

The 4-pole configuration has the neutral on the left (fixed position). Front connections both top and bottom, with a 35 mm connection pitch.

Sourcing posture

This is a standard catalogue item in the ComPacT NSX family. No last-time-buy window or phase-out notice applies.

Frequently asked questions

What is C10F4TM016C's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the F breaking capacity code in the NSX100F frame.

What standards does C10F4TM016C comply with?

EN/IEC 60947-2 for circuit breakers. It is also suitable for isolation per that standard, and carries pollution degree 3 per IEC 60664-1.

Where can I buy C10F4TM016C?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN