Skip to main content
Schneider Electric C10F4TM025C — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10F4TM025C ComPacT NSX100F, 25A, 4P, TM-

MPNC10F4TM025C
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 25 A, 4P, TM-D trip unit, 36 kA Icu at 415 V AC, toggle control.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM025C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM025C — Electrical
ParameterValue
[In] rated current25 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM025C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The C10F4TM025C is a Schneider Electric ComPacT NSX100F molded-case circuit breaker with a 25 A thermal-magnetic TM-D trip unit, 4 poles, and a breaking capacity code of F — 36 kA Icu at 415 V AC. It's designed for distribution applications in commercial and industrial panels, mounted on a backplate with front-facing connections.

The F-frame delivers 85 kA Icu at 220/240 V AC, 36 kA at 380/415 V, 35 kA at 440 V, 25 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V AC — all per IEC 60947-2.

The TM-D trip unit provides thermal-magnetic protection: the L curve handles overloads (thermal, adjustable), and the I curve covers short-circuits (magnetic, fixed). Rated 25 A at 50 °C, it's suited for protecting feeder circuits or downstream sub-distribution boards. Neutral protection is set at 1 x Ir for 4-pole configurations.

Mechanical durability is 50,000 cycles; electrical durability varies with voltage and load — 50,000 cycles at 440 V at half rated current, 30,000 at full rated current, and 10,000 at 690 V full rated. It's certified for isolation per EN/IEC 60947-2, meaning it can be used as a visible-break disconnect in the circuit.

Frequently asked questions

What is C10F4TM025C's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC per IEC 60947-2, which is the F breaking capacity code for this NSX100F frame.

Where can I buy C10F4TM025C?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What standards does C10F4TM025C comply with?

It complies with EN/IEC 60947-2 for circuit-breaker performance and isolation, IEC 60664-1 for pollution degree 3, and IEC 62262 for IK07 impact resistance.

MPN
C10F4TM025C