Skip to main content
Schneider Electric C10F4TM032C — Molded Case Circuit Breakers (MCCB)

C10F4TM032C ComPacT NSX100F 32A 4P Thermal-Magnetic, 36kA 41

MPNC10F4TM032C
Active

Schneider Electric ComPacT NSX100F, 4-pole 32 A thermal-magnetic MCCB, 85 kA Icu at 240 V, 36 kA Icu at 415 V, TM-D trip unit, IP40, backplate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM032C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM032C — Electrical
ParameterValue
[In] rated current32 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM032C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

What a 32 A TM-D MCCB means for your panel

That TM-D means it gives you overload protection (thermal element) and short-circuit protection (magnetic element) in one package, no separate relay or CT needed. The 32 A rating is at 50 °C, so if your panel runs hotter than that, you'll want to check the derating curve in the IEC 60947-2 documentation.

Breaking capacity: what the F code gets you

Mounts to a backplate, not a DIN rail — so you'll need a panel-mounting kit or a mounting plate drilled for the 140 mm width and 161 mm height. Connections are front-facing both top and bottom, which makes wiring and inspection straightforward in a row of breakers. The toggle handle gives clear visual indication of tripped vs on/off state.

Frequently asked questions

What is C10F4TM032C's breaking capacity at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the F breaking capacity code.

MPN
C10F4TM032C