Schneider Electric C10F4TM040 — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10F4TM040 ComPacT NSX 40A MCCB, 85kA

MPNC10F4TM040
Active

Schneider Electric ComPacT NSX, C10F4TM040, 4P MCCB, 40 A TM-D trip unit, 85 kA Icu at 240 V AC, backplate mount.

$199.09 – $547.78Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM040 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM040 — Electrical
ParameterValue
[In] rated current40 A at 40 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM040 — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The C10F4TM040 is a Schneider Electric ComPacT NSX100F moulded-case circuit breaker, 4-pole, rated 40 A at 40 °C with a TM-D thermal-magnetic trip unit. It carries an 85 kA Icu breaking capacity at 240 V AC and 36 kA at 415 V AC, per EN/IEC 60947-2.

Breaking capacity and what it means for your panel

For a 480 V AC panel (common in North America), the UL 60947-4-1 listing shows 25 kA Icu — enough for most downstream feeder applications. If you need selective coordination, you'd step up to a ComPacT NSX with an electronic Micrologic trip unit.

Mounting and integration into a panel

Mounts to a backplate — not a DIN rail — via the four M6 or M8 bolts through the base. The 140 mm width and 161 mm height fit the standard ComPacT NSX cutout; depth is 86 mm. Front connections both top and bottom simplify bus-bar or cable landing. IP40 enclosure protection means it's suited for a clean indoor panel; IK07 impact rating handles accidental tool drops during commissioning.

The C10F4TM040 is listed as current production. It is a standard catalogue item in the ComPacT NSX range.

Frequently asked questions

What compliance documentation does Schneider provide for C10F4TM040?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries IP40 and IK07 ratings. RoHS and REACH declarations are standard for the ComPacT NSX range; request them with your RFQ.

MPN