Skip to main content
Schneider Electric C10F4TM040C — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10F4TM040C ComPacT NSX100F MCCB, 40A, 36

MPNC10F4TM040C
Active

Schneider Electric ComPacT NSX100F, 4P, 40 A at 50 °C, TM-D trip unit, 36 kA Icu at 415 V AC, IP40, toggle control.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM040C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM040C — Electrical
ParameterValue
[In] rated current40 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM040C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10F4TM040C is a ComPacT NSX100F 4-pole moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 40 A at 50 °C. This is a Category A breaker — not intended for deliberate current making/breaking under fault, but for automatic fault interruption in a distribution feeder. IP40 enclosure protection and IK07 impact resistance suit indoor panel environments where occasional tool drops or dust ingress are a concern.

The 36 kA Icu at 415 V AC is the standard breaking capacity for a 400 V distribution board; the 85 kA at 240 V AC covers high-fault US-style 240/120 V services. Electrical durability is 50,000 cycles at 440 V In/2 and 30,000 cycles at 440 V In — sufficient for most distribution applications where switching cycles are infrequent. Relative humidity tolerance of 0...95 % covers most non-condensing indoor environments.

Frequently asked questions

Who supplies C10F4TM040C and how is it quoted for volume purchases?

This part is sourced through independent distribution channels and is quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is C10F4TM040C's breaking capacity at 415 V AC?

The C10F4TM040C has a breaking capacity of 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What compliance documentation does this brand provide for C10F4TM040C?

The breaker is designed to EN/IEC 60947-2 standards. It carries IP40 and IK07 ratings, and is suitable for isolation per the same standard. Specific RoHS/REACH/UL declarations should be confirmed at order time from the manufacturer's documentation portal.

MPN
C10F4TM040C