Specifications

Identification

C10F4TM063 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F4TM063 — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F4TM063 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F4TM063 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F4TM063 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F4TM063 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F4TM063 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10F4TM063 is a ComPacT NSX100F frame circuit breaker with a 63 A thermal-magnetic TM-D trip unit, 4 poles, and an F breaking capacity code — meaning 36 kA Icu at 415 V AC. That 36 kA interrupting rating at 415 V is the figure that governs selectivity coordination in a 400 V distribution board; the breaker also carries 85 kA Icu at 240 V and 25 kA at 480 V (UL 60947-4-1), so it slots into both IEC and UL-labeled installations without a separate SCCR derate for the same frame.

Front connections both upside and downside; connection pitch is 35 mm. The 4-pole version with neutral on the left (fixed position) fits standard 140 mm wide panel cutouts.

Durability and environmental limits

Mechanical endurance is 50,000 cycles; electrical endurance at 440 V rated current is 30,000 cycles — enough for frequent switching in a distribution board feeding motor loads or lighting contactors. IP40 enclosure rating and IK07 impact resistance handle typical panel environments; relative humidity up to 95% is accommodated without derating. Operating altitude to 2000 m without derating, with derating curves above that.

Frequently asked questions

What is C10F4TM063's breaking capacity at 415 V?

The C10F4TM063 carries 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What compliance documentation does this brand provide for C10F4TM063?

The C10F4TM063 is certified to EN/IEC 60947-2 and UL 60947-4-1, with suitability for isolation per those standards. Pollution degree 3 per IEC 60664-1 and overvoltage category III are documented.