It carries a 63 A thermal-magnetic TM-D trip unit. Breaking capacity is 85 kA Icu at 240 V AC, 36 kA Icu at 415 V AC, and 8 kA Icu at 690 V AC — all per IEC 60947-2. Four poles, toggle control, front-connected.
Connection pitch is 35 mm between poles. Neutral is on the left. IP40 enclosure protection, IK07 impact resistance. Overvoltage category III.
Mechanical durability is 50,000 cycles; electrical durability ranges from 50,000 cycles at 440 V at half rated current down to 10,000 cycles at 690 V at full rated current. Operating altitude is 0 to 2000 m without derating, 2000 to 5000 m with derating. Relative humidity 0 to 95%.