Schneider Electric C10F4TM080C — Molded Case Circuit Breakers (MCCB)

Schneider C10F4TM080C ComPacT NSX 80A MCCB, 36kA 415V

MPNC10F4TM080C
Active

Schneider Electric ComPacT NSX, NSX100F, MCCB, 4P, 80 A TM-D trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F4TM080C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F4TM080C — Electrical
ParameterValue
[In] rated current80 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F4TM080C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

80 A MCCB for distribution boards — the so-what on the ratings

That rating puts it squarely in the industrial panel main or large-feeder role, not a branch-device slot. The neutral protection is set at 1 x Ir (full-rated current) — common for distribution where you want the neutral protected at the same level as the phases. No earth-leakage module built in; if you need ground-fault protection, that's an add-on Vigi block.

The Icu curve tells you where this breaker fits in a coordinated system. At 220/240 V AC it's rated 85 kA — high enough for most secondary substations. At 380/415 V AC it's 36 kA, at 440 V it's 35 kA, then it drops to 25 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V.

Mounting and integration — backplate, front connections, IK07

Mounts on a backplate — no DIN-rail clip on this frame. Both line and load connections are front-accessible, which keeps wiring neat in a row of breakers. IK07 impact resistance handles accidental tool drops during commissioning.

Standards and approvals — what the compliance marks mean

That covers the interrupting ratings, the isolation suitability (marked 'suitable for isolation' per the standard), and the utilisation category A (non-delayed, no intentional short-time delay).

Durability — electrical and mechanical cycles

Mechanical endurance is 50,000 cycles. Electrical endurance depends on the voltage and current being switched: 50,000 cycles at 440 V at half rated current, 30,000 at full rated current at 440 V, 20,000 at 690 V at half current, and 10,000 at full 690 V. That's typical for a distribution MCCB — it's not a contactor meant for frequent motor starting, but it handles regular switching of the feeder circuit.

Frequently asked questions

Where can I buy C10F4TM080C and how is it quoted?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no blanket stock or price figure applies here.

What is the breaking capacity of C10F4TM080C at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That's the 'F' breaking capacity code — the most common rating for this frame in European distribution panels.

What does the TM-D trip unit protect against?

L for overload protection (thermal) and I for short-circuit protection (magnetic). It's a fixed thermal-magnetic unit — no electronic adjustments, no interchangeable rating plugs. The 80 A rating is fixed at the factory.

What compliance documentation does Schneider provide for C10F4TM080C?

The breaker is certified to EN/IEC 60947-2, rated for isolation per that standard, and carries pollution degree 3 and overvoltage category III ratings. Specific RoHS/REACH declarations would be part of the Schneider documentation package available on request.