Skip to main content
Schneider Electric C10F4TM080C — Miniature Circuit Breakers (MCB)

Schneider C10F4TM080C ComPacT NSX 80A MCCB, 36kA 415V

MPNC10F4TM080C
Active

Schneider Electric ComPacT NSX, NSX100F, MCCB, 4P, 80 A TM-D trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F4TM080C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F4TM080C — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F4TM080C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F4TM080C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F4TM080C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F4TM080C — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F4TM080C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

80 A MCCB for distribution boards — the so-what on the ratings

That rating puts it squarely in the industrial panel main or large-feeder role, not a branch-device slot. The neutral protection is set at 1 x Ir (full-rated current) — common for distribution where you want the neutral protected at the same level as the phases. No earth-leakage module built in; if you need ground-fault protection, that's an add-on Vigi block.

The Icu curve tells you where this breaker fits in a coordinated system. At 220/240 V AC it's rated 85 kA — high enough for most secondary substations. At 380/415 V AC it's 36 kA, at 440 V it's 35 kA, then it drops to 25 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V.

Mounting and integration — backplate, front connections, IK07

Mounts on a backplate — no DIN-rail clip on this frame. Both line and load connections are front-accessible, which keeps wiring neat in a row of breakers. IK07 impact resistance handles accidental tool drops during commissioning.

Standards and approvals — what the compliance marks mean

That covers the interrupting ratings, the isolation suitability (marked 'suitable for isolation' per the standard), and the utilisation category A (non-delayed, no intentional short-time delay).

Durability — electrical and mechanical cycles

Mechanical endurance is 50,000 cycles. Electrical endurance depends on the voltage and current being switched: 50,000 cycles at 440 V at half rated current, 30,000 at full rated current at 440 V, 20,000 at 690 V at half current, and 10,000 at full 690 V. That's typical for a distribution MCCB — it's not a contactor meant for frequent motor starting, but it handles regular switching of the feeder circuit.

Frequently asked questions

Where can I buy C10F4TM080C and how is it quoted?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no blanket stock or price figure applies here.

What is the breaking capacity of C10F4TM080C at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That's the 'F' breaking capacity code — the most common rating for this frame in European distribution panels.

What does the TM-D trip unit protect against?

L for overload protection (thermal) and I for short-circuit protection (magnetic). It's a fixed thermal-magnetic unit — no electronic adjustments, no interchangeable rating plugs. The 80 A rating is fixed at the factory.

What compliance documentation does Schneider provide for C10F4TM080C?

The breaker is certified to EN/IEC 60947-2, rated for isolation per that standard, and carries pollution degree 3 and overvoltage category III ratings. Specific RoHS/REACH declarations would be part of the Schneider documentation package available on request.

MPN
C10F4TM080C