Skip to main content
Schneider Electric C10F4TM100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F4TM100 ComPacT NSX100F, 100A, 4P, 36k

MPNC10F4TM100
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 100 A, 4P, 36 kA Icu at 415 V AC, TM-D trip unit.

$218.86 – $608.20Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F4TM100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F4TM100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F4TM100 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F4TM100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F4TM100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F4TM100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F4TM100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It's rated for distribution duty in commercial and industrial panels, built to EN/IEC 60947-2.

Breaking capacity drops as voltage climbs: 85 kA Icu at 240 V AC, 36 kA at 415 V, 25 kA at 500 V, and 8 kA at 690 V. The NSX100F sits below the NSX160F and NSX250F in the same ComPacT family; stepping up to those buys higher ampacity without changing the footprint.

Front connections top and bottom, 35 mm connection pitch. The 4-pole body is 140 mm wide, 161 mm high, 86 mm deep. IP40 enclosure protection, IK07 impact rating.

Mechanical endurance is 50,000 cycles; electrical endurance at rated current and 440 V is 30,000 cycles — that's a solid duty cycle for a distribution breaker that isn't switched daily.

Frequently asked questions

Where can I buy C10F4TM100 and get a price?

The C10F4TM100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C10F4TM100 at 415 V?

The C10F4TM100 has a breaking capacity of 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the F-code rating that determines its suitability for most European 400 V distribution panels.

What compliance documentation does Schneider provide for C10F4TM100?

The C10F4TM100 is certified to EN/IEC 60947-2 and carries a suitability-for-isolation declaration per that standard. It is rated for pollution degree 3 and overvoltage category III. Specific RoHS/REACH declarations are available from Schneider's documentation portal for this order code.

MPN