Schneider Electric C10F6TM016C — Miniature Circuit Breakers (MCB)

C10F6TM016C ComPacT NSX100F 16A 4P Circuit Breaker, 36 kA 41

MPNC10F6TM016C
Active

Schneider Electric ComPacT NSX NSX100F, 16 A, 4P, thermal-magnetic TM-D trip unit, 36 kA Icu at 415 V AC, IP40, toggle control.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F6TM016C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F6TM016C — Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F6TM016C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F6TM016C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F6TM016C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F6TM016C — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F6TM016C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D trip gives you fixed thermal overload (L) and fixed magnetic short-circuit (I) protection; no adjustment dials, so what you order is what protects the circuit. The 4-pole configuration (3 phases + neutral) suits a 3-phase 4-wire system where the neutral is switched. Mounts on a backplate, not a DIN rail — this is a bolted-down MCCB for a panel or enclosure, with front connections top and bottom. The 140 mm width, 161 mm height, and 86 mm depth fit the standard NSX100F cutout. The IK07 impact rating means it withstands a 2 J hammer blow — robust enough for an industrial panel door.

Compliance and approvals

Suitability for isolation is confirmed per that standard — you can use it as a disconnecting means. No earth-leakage protection built in — the TM-D trip handles overload and short-circuit only. If you need ground-fault protection, you add a Vigi module externally. The breaker is rated for horizontal and vertical mounting, flat on the backplate, which gives flexibility in panel layout.

Frequently asked questions

What is the breaking capacity of C10F6TM016C at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the F breaking capacity code — the standard rating for this frame size at 415 V.

What does the TM-D trip unit protect against?

Thermal overload (L) and fixed magnetic short-circuit (I). No adjustment — the thermal element is sized for 16 A at 50 °C, and the magnetic pickup is fixed at a factory-set multiple of In.