Skip to main content
Schneider Electric C10F6TM025C — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10F6TM025C ComPacT NSX100F MCCB, 25 A, 3

MPNC10F6TM025C
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 4P, 25 A, TM-D trip unit, 36 kA Icu at 415 V AC, toggle control, backplate mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F6TM025C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F6TM025C — Electrical
ParameterValue
[In] rated current25 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F6TM025C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10F6TM025C is a ComPacT NSX100F moulded-case circuit breaker (MCCB) with a 25 A thermal-magnetic TM-D trip unit, four poles, and a 36 kA interrupting rating at 415 V AC.

The TM-D unit provides thermal overload protection (L) and magnetic short-circuit protection (I), a standard combination for feeder and branch-circuit protection in distribution panels. Breaking capacity is the key selection parameter for fault duty. At 415 V AC — common in European industrial networks — the C10F6TM025C delivers 36 kA Icu. At 220/240 V the rating rises to 85 kA; at 690 V it drops to 8 kA. Selectivity studies should use the voltage closest to the actual system. Rated for 50,000 mechanical cycles and 30,000 electrical cycles at rated current (440 V In), this breaker is built for panel duty where occasional switching is expected, not continuous motor-starting service.

The 140 mm width for a 4-pole frame is standard for the NSX100 footprint. IP40 enclosure protection and IK07 impact resistance suit it for enclosed panel installation where occasional tool contact or debris is a concern. The toggle control provides local manual operation.

Frequently asked questions

What is the breaking capacity of C10F6TM025C at 415 V?

At 380/415 V AC 50/60 Hz, the C10F6TM025C has a breaking capacity (Icu) of 36 kA per IEC 60947-2.

What standards does C10F6TM025C comply with?

The C10F6TM025C complies with EN/IEC 60947-2 and is suitable for isolation per that standard.

Where can I buy C10F6TM025C and get current pricing?

The C10F6TM025C is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C10F6TM025C