Schneider Electric C10F6TM040C — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10F6TM040C ComPacT NSX 40A MCCB, 36kA 41

MPNC10F6TM040C
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 40 A, 4P, TM-D trip unit, 36 kA Icu at 415 V AC, toggle control.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10F6TM040C — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10F6TM040C — Electrical
ParameterValue
[In] rated current40 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10F6TM040C — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameNSX100F
StandardsEN/IEC 60947-2

Product details

The C10F6TM040C is a Schneider Electric ComPacT NSX100F moulded-case circuit breaker with a 40 A thermal-magnetic TM-D trip unit, four poles, and a 36 kA interrupting capacity at 415 V AC. The 40 A rating at 50 °C covers typical lighting, small motor, or general distribution loads without derating in a warm enclosure.

At 220/240 V it jumps to 85 kA Icu, and at 690 V it still holds 8 kA Icu. That spread means the same breaker can be used across different voltage levels in the same plant without swapping frames. The utilisation category A (non-selectivity-oriented) means it's designed to clear faults fast rather than coordinate with downstream devices — fine for a main or branch breaker where you want quick trip, not for a selective main where you need time delay.

Mounts flat on a backplate — no DIN rail here. The 140 mm width and 161 mm height fit standard MCCB cutouts in distribution boards. IP40 front face keeps out tools and fingers; IK07 impact rating means it survives a 2 J hammer blow — fine for a locked electrical room but not for a washdown area.

Durability and duty cycles

Rated for 50,000 mechanical operations and 30,000 electrical cycles at rated current (40 A, 440 V). That's a solid 10+ years of daily switching in a machine-tool or conveyor application. At half rated current (20 A) the electrical endurance doubles to 50,000 cycles — typical for lightly loaded feeder breakers that cycle with the shift schedule.

Frequently asked questions

Where can I buy C10F6TM040C and get a price?

This part is sourced to order against an RFQ through independent industrial distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the breaking capacity of C10F6TM040C at 415 V?

36 kA Icu at 380/415 V AC, 50/60 Hz, per IEC 60947-2. At 440 V it's 35 kA; at 500 V it's 25 kA.

What compliance documentation does this breaker carry?

It meets EN/IEC 60947-2, is suitable for isolation per that standard, and carries IP40 and IK07 ratings. Pollution degree 3 per IEC 60664-1. No earth-leakage protection built in.

MPN
C10F6TM040C