Skip to main content
Schneider Electric C10F6TM063 — Miniature Circuit Breakers (MCB)

Schneider C10F6TM063 ComPacT NSX 63A, 36kA at 415V MCCB

MPNC10F6TM063
Active

Schneider Electric ComPacT NSX, NSX100F, circuit breaker, 63 A at 40 °C, thermal-magnetic TM-D trip unit, 36 kA Icu at 415 V AC, 4P, EN/IEC 60947-2.

$185.33 – $534.01Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F6TM063 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F6TM063 — Ratings
ParameterValue
Rated current (In)63 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F6TM063 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F6TM063 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F6TM063 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F6TM063 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F6TM063 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C10F6TM063 is a ComPacT NSX100F moulded-case circuit breaker rated 63 A at 40 °C with a thermal-magnetic TM-D trip unit. It delivers 36 kA Icu at 415 V AC — the F breaking capacity code — and carries a full 85 kA Icu at 240 V AC. This is a current-production part, still active on Schneider's catalog.

The 36 kA Icu at 415 V AC (EN/IEC 60947-2) is the figure that governs panel coordination in a 400 V distribution board. That's the SCCR you size upstream fuses or a transformer against. At 240 V it jumps to 85 kA, so if your service entrance is 240 V delta you have substantial headroom for fault currents from a large transformer. The thermal element tracks RMS heating for overloads; the magnetic element responds instantaneously to short-circuit currents. No earth-leakage function is integrated — the neutral protection setting is 3D (no protection). If you need ground-fault, add a Vigi module externally.

The 4-pole body measures 140 mm wide × 161 mm high × 86 mm deep — a standard ComPacT NSX footprint that fits existing Schneider panel cutouts. IP40 front face (IP40 conforming to IEC 60529) keeps dust out of the enclosure; IK07 impact rating means it survives a tool drop during commissioning.

Frequently asked questions

What standards does C10F6TM063 comply with?

It is certified to EN/IEC 60947-2 and UL 60947-4-1. Suitability for isolation is confirmed per EN/IEC 60947-2. Pollution degree 3 per IEC 60664-1.

What is the breaking capacity of C10F6TM063 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. At 240 V it is 85 kA Icu; at 690 V it drops to 8 kA Icu.

Where can I buy C10F6TM063 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
C10F6TM063