Four poles, toggle control, front-connected terminals. This is a current-production part, not an end-of-life line.
What the breaking capacity means for your panel
At 415 V AC, the C10F6TM080 delivers 36 kA Icu per IEC 60947-2.
The 140 mm width × 161 mm height × 86 mm depth fits standard panel layouts. Enclosure protection is IP40 (finger-safe, no gasket) and IK07 impact resistance.
Durability and electrical life
Rated for 50,000 mechanical operations and 30,000 electrical cycles at 440 V at rated current (In). At half load (In/2) at 440 V, electrical durability jumps to 50,000 cycles. At 690 V, expect 10,000 cycles at In and 20,000 at In/2. These numbers assume resistive or mixed loads; motor switching or high inrush will reduce service life.
Overvoltage category III (distribution-level). Suitable for isolation. Pollution degree 3. The breaking capacities are also listed with UL 60947-4-1 references at 240 V (85 kA), 480 V (25 kA), and 600 V (10 kA), indicating UL recognition for the US market. No earth-leakage protection built in — add a Vigi module if ground-fault protection is required.