Schneider Electric C10F6TM080 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F6TM080 ComPacT NSX MCCB, 80 A, 4P, 36

MPNC10F6TM080
Active

Schneider Electric ComPacT NSX, NSX100F, MCCB, 80 A, 4P, TM-D trip, 36 kA Icu at 415 V AC, EN/IEC 60947-2.

$301.59 – $579.47Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F6TM080 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F6TM080 — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F6TM080 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F6TM080 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F6TM080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F6TM080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F6TM080 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Four poles, toggle control, front-connected terminals. This is a current-production part, not an end-of-life line.

What the breaking capacity means for your panel

At 415 V AC, the C10F6TM080 delivers 36 kA Icu per IEC 60947-2.

The 140 mm width × 161 mm height × 86 mm depth fits standard panel layouts. Enclosure protection is IP40 (finger-safe, no gasket) and IK07 impact resistance.

Durability and electrical life

Rated for 50,000 mechanical operations and 30,000 electrical cycles at 440 V at rated current (In). At half load (In/2) at 440 V, electrical durability jumps to 50,000 cycles. At 690 V, expect 10,000 cycles at In and 20,000 at In/2. These numbers assume resistive or mixed loads; motor switching or high inrush will reduce service life.

Overvoltage category III (distribution-level). Suitable for isolation. Pollution degree 3. The breaking capacities are also listed with UL 60947-4-1 references at 240 V (85 kA), 480 V (25 kA), and 600 V (10 kA), indicating UL recognition for the US market. No earth-leakage protection built in — add a Vigi module if ground-fault protection is required.

Frequently asked questions

What is the breaking capacity of the C10F6TM080 at 415 V?

36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the ultimate breaking capacity — the breaker can safely interrupt one fault at that level.

What does the TM-D trip unit protect against?

Thermal overload (L) via bimetal and magnetic short-circuit (I) via solenoid. Fixed settings — no field adjustment on the trip curve.

What is the physical size of the C10F6TM080?

140 mm wide × 161 mm high × 86 mm deep. Fits standard backplate mounting in horizontal or vertical orientation.

Is the C10F6TM080 suitable for isolation?

Yes, it is marked suitable for isolation per EN/IEC 60947-2, with a visible contact position indicator.