Skip to main content
Schneider Electric C10F6TM100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10F6TM100 ComPacT NSX 100A MCCB, 36kA 41

MPNC10F6TM100
Active

Schneider Electric ComPacT NSX, C10F6TM100, 4P 100A thermal-magnetic MCCB, 36 kA Icu at 415 V AC, toggle control, backplate mount.

$202.00 – $595.30Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

C10F6TM100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution

Ratings

C10F6TM100 — Ratings
ParameterValue
Rated current (In)100 A at 50 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII

Protection

C10F6TM100 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles

Mechanical

C10F6TM100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle

Environmental

C10F6TM100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %

Approvals

C10F6TM100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Specifications

C10F6TM100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The TM-D unit provides L (thermal) overload protection and I (magnetic) short-circuit protection, so it handles motor inrush and distribution feeder duty equally. Breaking capacity is where this part earns its place in the panel. At 415 V AC — the most common industrial distribution voltage — it delivers 36 kA Icu. For a 400 V panel with a transformer upstream that can deliver 35 kA of fault current, this breaker holds coordination without cascading to the main. The 4-pole (4P) configuration with neutral on the left and no integral earth-leakage module means this is a straight distribution or feeder breaker — not a GFCI. Neutral protection is set to 3D (no protection), so the neutral pole is switched but not monitored for overcurrent; confirm your system grounding design before specifying.

Mounting and integration — backplate, front connections, IP40

Front-facing connections for both line and load sides simplify bus-bar routing and cable entry in a standard panel layout. IP40 and IK07 mean it is protected against tools and wires >1 mm and against 0.5 J impacts — fine for a clean indoor panel, not for washdown zones. Five equipment slots allow auxiliary contacts, shunt trips, or an under-voltage release to be added without removing the breaker from the panel.

Lifecycle and sourcing — active production, quoted to order

Lifecycle status is current — Schneider continues to manufacture the ComPacT NSX range. This is not a phase-out or NRND part. For volume purchases or BOM-line commitments, submit a request with target quantity and delivery window.

Compliance and approvals — IEC 60947-2, isolation suitability

Certified to EN/IEC 60947-2 with utilisation category A — suitable for distribution, not for motor starting under load.

Frequently asked questions

Who supplies C10F6TM100 and how is it quoted?

Sourced through independent distribution channels. Submit an RFQ with your target quantity and delivery window; availability and current pricing are confirmed at quote time.

What is the closest alternative to C10F6TM100 in the ComPacT NSX family?

Within the ComPacT NSX range, the closest alternative would be a different breaking-capacity code (e.g., an 'N' or 'S' frame) or a different trip-unit rating. The TM-D trip unit and 4-pole configuration are common across the family; the deciding factor is the required Icu at your system voltage.

What compliance documentation does Schneider provide for C10F6TM100?

The breaker is certified to EN/IEC 60947-2 and is suitable for isolation per that standard. Standard Schneider documentation includes a Declaration of Conformity covering the applicable EU directives. For specific RoHS or REACH declarations, request them at quote time.

MPN
C10F6TM100