Skip to main content
Schneider Electric C10H3TM080 — Miniature Circuit Breakers (MCB)

Schneider C10H3TM080 ComPacT NSX100H 80A 3P MCCB, 100 kA

MPNC10H3TM080
Active

Schneider Electric ComPacT NSX, NSX100H, circuit breaker, 80 A, 3P, thermal-magnetic TM-D trip, 100 kA Icu at 240 V AC, IEC 60947-2.

$264.06 – $595.94Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10H3TM080 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10H3TM080 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10H3TM080 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10H3TM080 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10H3TM080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10H3TM080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10H3TM080 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

80 A MCCB for distribution panels — what the ratings mean

It is designed for distribution applications in commercial and industrial panels, mounted on a backplate in either horizontal or vertical orientation. At the more common 415 V AC three-phase level it still holds 70 kA Icu, which covers most secondary distribution scenarios where the transformer is close to the panel. The TM-D trip unit provides thermal overload protection (L) and magnetic short-circuit protection (I). The magnetic trip threshold is fixed within the TM-D characteristic — no interchangeable trip units or electronic adjustments on this variant.

Front connections on both line and load sides simplify bus-bar and cable routing. The 35 mm connection pitch matches common distribution block spacing. IP40 enclosure protection and IK07 impact resistance are adequate for enclosed panel mounting; no washdown rating, so keep it inside the cabinet. Mechanical durability is 50,000 cycles, electrical durability varies by load — 30,000 cycles at rated current (80 A, 440 V) and 50,000 at half load.

The UL ratings are 85 kA Icu at 240 V AC, 65 kA at 480 V AC, and 10 kA at 600 V AC — useful when the same part number must serve both IEC and UL panel builds.

Frequently asked questions

Where can I buy C10H3TM080 and get a price?

The C10H3TM080 is sourced and quoted to order through independent distribution. Submit an RFQ to confirm current availability and pricing — no stock figures or lead-time numbers are published here.

What is the breaking capacity of C10H3TM080 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it drops to 65 kA, and at 690 V to 10 kA.

Does C10H3TM080 include earth-leakage protection?

No. The TM-D trip unit provides only thermal overload and magnetic short-circuit protection. Earth-leakage protection is not integrated — a separate Vigi add-on block or external RCD is required.

What compliance documentation does Schneider provide for C10H3TM080?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. Standard documentation includes the IEC declaration of conformity and UL recognition. RoHS and REACH compliance are covered by Schneider's general product compliance statements for the ComPacT NSX range.

MPN