IP40 enclosure protection keeps dust out of a panel; if this goes into a washdown area, it needs a higher-rated enclosure around it. Toggle control, no motor operator or rotary handle by default.
C10H3TM063 ComPacT NSX 63A MCCB, 100kA 240V, TM-D Trip Unit
MPNC10H3TM063
Active
Schneider Electric ComPacT NSX, NSX100H MCCB, 3P, 63 A, TM-D trip unit, 100 kA Icu at 240 V AC, backplate mount.
$251.64 – $558.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product name | ComPacT NSX |
| Product range | ComPacT |
| Product/component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 63 A at 40 °C |
| Poles configuration | 3P |
| Breaking capacity | 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
| Rated service breaking capacity (Ics) | 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Without |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Electrical durability (cycles) | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
| Mechanical durability (cycles) | 50000 cycles |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Control type | Toggle |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 0...95 % |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Trip unit protection functions | LI |
Product details
Frequently asked questions
What is the breaking capacity of C10H3TM063 at 480V?
65 kA Icu at 480 V AC, per UL 60947-4-1 listing.
What documentation is available for C10H3TM063?
Standards compliance includes EN/IEC 60947-2, UL 60947-4-1, and IEC 62262 for IK07 impact rating. Pollution degree 3 per IEC 60664-1. Isolation suitability confirmed per EN/IEC 60947-2.
MPN