Skip to main content
Schneider Electric C10R35E040 — Molded Case Circuit Breakers (MCCB)

Schneider Electric C10R35E040 ComPacT NSX, 40 A, 200 kA, 3P

MPNC10R35E040
Active

Schneider Electric, ComPacT NSX, MCCB, C10R35E040, 40 A, 200 kA Icu at 415 V AC, 3P, MicroLogic 5.2 E electronic trip unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

C10R35E040 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
C10R35E040 — Electrical
ParameterValue
[In] rated current40 A at 40 °C
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz
[Ui] rated insulation voltage800 V AC 50/60 Hz
C10R35E040 — Specifications
ParameterValue
Poles description3P
Trip unit nameMicroLogic 5.2 E
Trip unit technologyElectronic
Device short nameNSX100R
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10R35E040 is a ComPacT NSX100R molded-case circuit breaker (MCCB) with a MicroLogic 5.2 E electronic trip unit, rated 40 A at 40 °C. The MicroLogic 5.2 E trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves, plus integrated energy metering and power-quality data communication — so this breaker doubles as a panel-mounted power monitor, reporting instantaneous and demand values, time-stamped events, and energy totals over its communication bus. The 20-minute thermal memory before and after tripping means the breaker remembers its thermal history, preventing nuisance re-closure on a still-hot conductor.

Where it is used and deployment context

This MCCB is designed for distribution applications (device application: Distribution) in industrial and commercial switchboards. The IP40 front-panel protection and IK07 impact resistance suit it for enclosed panel installations where occasional contact or debris is expected but not washdown.

Frequently asked questions

How do I get current pricing and availability for C10R35E040?

Submit an RFQ through this listing. The part is sourced and quoted to order; pricing and stock levels are confirmed at quote time.

What is the breaking capacity of C10R35E040 at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, which is the highest breaking capacity code (R) in the ComPacT NSX range.

What protection curves does the MicroLogic 5.2 E trip unit provide?

It provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection, plus energy metering and power-quality communication.

What are the mounting dimensions of C10R35E040?

Height 161 mm, width 105 mm, depth 86 mm. It mounts on a backplate in horizontal or vertical orientation with front connections.

MPN