Skip to main content
Schneider Electric C10W35E040 — Miniature Circuit Breakers (MCB)

Schneider Electric C10W35E040 ComPacT NSX, 40 A, 100 kA, Mic

MPNC10W35E040
Active

Schneider Electric ComPacT NSX, 3P, 40 A, 100 kA Icu at 690 V AC, MicroLogic 5.2 E electronic trip unit, IEC 60947-2.

$13.51Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10W35E040 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10W35E040 — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10W35E040 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10W35E040 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10W35E040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10W35E040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10W35E040 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range18...40 A
Trip unit protection functionsLSI

Product details

The Schneider Electric C10W35E040 is a ComPacT NSX100HB2 molded-case circuit breaker, 3-pole, with a MicroLogic 5.2 E electronic trip unit rated 40 A at 40 °C. The electronic trip unit provides LSI protection (long-time overload, short-time short-circuit, instantaneous) plus energy metering, demand current/power, and time-stamped event logs, so it doubles as a panel-level power monitor.

Where it is used and deployment context

The 105 mm width, 161 mm height, and 86 mm depth fit a typical MCCB slot in a multi-breaker lineup.

The MicroLogic 5.2 E trip unit offers adjustable long-time pickup (Ir), long-time delay (tr), short-time pickup (Isd) and delay (tsd), and instantaneous pickup (Ii). This allows selective coordination with downstream breakers — the 20-minute thermal memory before and after tripping prevents nuisance re-closure on hot conductors.

Frequently asked questions

Where can I buy C10W35E040 and how do I get a price?

The C10W35E040 is available to source through independent distribution. Submit an RFQ for a current price and availability quote.

What is the breaking capacity of C10W35E040?

The C10W35E040 has a breaking capacity of 100 kA Icu at 690 V AC 50/60 Hz per IEC 60947-2.

What compliance documentation does C10W35E040 have?

The C10W35E040 is certified to EN/IEC 60947-2, with IP40 and IK07 protection ratings per IEC 60529 and IEC 62262.

MPN
C10W35E040