Skip to main content
Schneider Electric C10W3MA100

Schneider Electric C10W3MA100

MPNC10W3MA100
Active

C10W3MA100 - COMPACT NSX100HB2 by SQUARE D

$421.64Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10W3MA100 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeI : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Current100 A at 65 °C
Breaking capacity codeHB2 100 kA 690 V AC

All specifications

C10W3MA100 additional specifications
ParameterValue
[Ics] rated service breaking capacity100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Power dissipation per pole5.2 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth86 mm
Width105 mm
Height161 mm
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameMA
Number of slots5 slot(s)
Trip unit rating100 A at 65 °C
Device short nameNSX100HB2
Device applicationMotor protection
Overvoltage categoryIII
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Isd] short-time protection pick-up adjustment range6...14 x In
[Ii] instantaneous protection pick-up adjustment range6...14 x In
MPN